Specifications
28
90x107.5x64.5mm (WM14 DIN) (6-DIN mod.)
96x96x61.5mm (WM14 96)
LED, h: 14mm
YES
3 DGTs
8+1 DGTs
5+2 DGTs
W-VA:±(1% F.S.+1DGT)
var:±(2% F.S. +1DGT)
V
LL: ±(1.5% F.S. +1DGT)
V
LN-A:±(0.5% F.S. +1DGT)
kWh: cl. 1(Adv), 2(Bas); kvarh: cl. 2(Adv), 3(Bas)
≤200ppm/°C
1.5 times/s
Unbalanced: 2-3-phase; bal.: 1-3-ph.
100/208VAC; 400/660VAC
5AAC; Basic: shunts or CT’s depending
on the model. Advanced: shunts
Prog.: CT up to 5,000A; VT up to 10kV
TRMS method
Sys: VLL, An, W, var, VA, Wdmd,Wdmd max,VAdmd, Hz
Wh, varh, h. Single-phase: VLL,VLN,A,
W, var, VA, PF, Admd,Admd max
THD up to the 16th harmonics (V and A)
2 (open collector)
16 with OR/AND function (2 relays)
N.A.
RS422/485 (Modbus), Profibus DP V0
Action: on variables and outputs
Basic version: with Profibus on request
Adv. vers.: with pulses or alarms on req.
Basic: 24, 48,115, 230VAC;
Adv.: 18 to 60VAC/DC, 90 to 260VAC/DC
CE, cURus, cCSAus
IP40 (WM14 DIN); IP65 (WM14 96)
NEMA4x, NEMA12
Housing (H x W x D)
Display type
Variables on display
Instantaneous variables
Energy variables
Hours
Accuracy
Temperature drift
Refresh rate
System type
Voltage inputs (Un)
Current inputs (In)
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
WM14 DIN and WM14 96 available as Basic and Advanced
power analyzers can be used in all the applications where it
is needed to measure and control the main electrical
parameters and to transmit them by pulses, by serial
communication or Profibus DP to a PLC or a PC. WM14 is
compact and is available either for panel mounting or DIN-
rail mounting.
WM14 is the natural evolution of WM12. It maintains the
same advantages and measurement capabilities of the
multi function meter providing the following additional
features and benefits:
• Metering of both total and partial active and reactive
energies with pulse outputs in order to survey not only
the typical load parameters but also the consumptions.
• Measurement of the thermal current, by single phase,
and recording of the maximum demands. This
information will let the maintenance people know if the
over current protections (fuses, automatic switches,
etc.) are adequately preset and in case of trip which is
their real current.
• Hour counter meter function. On board of a machine or
a generating-set, the instrument shows how long those
machines are being used saving also the cost of an
external classical hour counter meter. A proper
“machine usage” cost and/or mechanical maintenance
can be estimated and planned.
• OR/AND control of up to 16 selected variables so to grant
an extended load or line control through 2 digital outputs.
Power Analyzers WM14 DIN WM14 96
Basic and Advanced functions
WM14 96 WM14 DIN
The histogram is related to the “Advanced” version.
Hardware Functions
In-Out
Performances
The best to suit your needs!
Comm
16
OROR
AND
96
DIN
• Basic version only
• Insulated current inputs
• Universal AC/DC power supply.