Specifications

25
96x96x61.4mm
LCD (2-colour with back light STN
technology), h: 9.5mm
YES
3x4 DGTs
8 DGTs
W-VA-PF: ±(1% RDG+2DGT)
var: ±(2% RDG+2DGT)
V
LN-A: ±(0.5% RDG+1DGT)
V
LL: ±(1.5% RDG+1DGT)
THD: ±(2% RDG+1DGT)
Class 1 (kWh) EN62053-21/B EN50470-3
Class 2 (kvarh) EN62053-23
200ppm/°C
1.5 times/s
Unbalanced: 2-3-phase; bal.:1-3-ph.
120/208VAC, 400/660VAC
In: 1/5A, Imax: 10AAC
3 independent (H
2O/gas counter or
4-time period selection)
Prog: CT up to 60k; VT up to 6000
TRMS method
Sys: VLL,VLN, An, Admd max, var, VA, Wdmd,
W
dmd max,VAdmd,VAdmd max, Hz. kWh, kvarh, h.
Single-phase: V
LL,VLN, A, W, var, VA, PF,
%THD-V, %THD-A, kWh, kvarh
THD up to 15th H (V and A)
3-open collector or 2-relay
3-open collector or 2-relay
N.A.
RS485 (2-wire, Modbus)
Action: on variables and outputs
Phase sequence indication and control
18 to 60VAC/DC, 90 to 260VAC/DC
CE, cULus, MID certification on request
IP50
Housing (H x W x D)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Refresh rate
System type
Voltage inputs (Un)
Current inputs (In/Imax)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
EM26 96 is a panel mounting Energy Analyzer for three
phase unbalanced systems capable to perform not only an
extended consumption analysis but also keeping under
control all the electrical parameters, Harmonics included.
Certifications on request:
EC Type examination, Annex B of MID (option"P")
MID Annex B+F (option "PF") for legal metrology
The main advantages:
Suitable to be mounted on any switch or control-gear by
means of only 46 mm housing behind the panel.
Wide angle variable readability by means of a sharp and
two colour back lighted LCD display (STN technology).
Better and more reliable energy measurements fulfilling
both the new European standards EN50470-3 and
EN62053-23.
Gas, hot-water, cold-water and remote heating
measurements thanks to its three digital inputs.
Extended energy measurements using total/partial or
total/multi-tariff metering.
Extended alarm control on any available variable by
means of up to three digital outputs with display warning
based on back light colour changing.
Load failure prevention thanks to the harmonic analysis
and control.
Easy programming using the application oriented
programming structure.
Easy variable scrolling by means of the front joystick.
Wide interfacing capability using up to 3 pulse outputs or
the RS485 communication port.
Energy Analyzer EM26 96
EM26 96
Hardware Functions
In-Out
Performances
The best to suit your needs!
Comm
MID certified for
legal metrology
(on request)