Specifications

20
Hardware
Functions
In-Out
Performances
The best to suit your needs!
Modular Energy Meter EM3 DIN
90x162.5x63mm (9-DIN modules)
Mechanical
YES
N.A.
6+1 DGT
Class 2 (EN61036)
Class 3 (EN61268)
250ppm/°C
N.A.
Unbalanced: 3-phase
120/208VAC, 230/400VAC, 380/660VAC
Ib: 20A, Imax: 100AAC
N.A.
N.A.
TRMS method
kWh or kvarh (selectable)
N.A.
2 (open collector type)
N.A.
N.A.
N.A.
N.A.
Start-up current: 80mAAC
Self power supply, 115VAC, 230VAC
CE
IP40
Housing (H x W x D)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Refresh Rate
System type
Voltage inputs (Un)
Current inputs (Ib/Imax)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
Easy installation avoiding any programming set-up.
Self power supply making the installation easier and
quicker.
Direct connection up to 100A allowing the user to save
the costs of external current transformers and of
relevant wiring.
Dual pulse output transmitting to a PLC or other
equipment the active and reactive energy
simultaneously.
Wall mounting avoiding any other protection enclosure.
Comm
100A
EM3 DIN
EM3 DIN is an energy meter that has been developed to
meet the requirements of those applications where a very
simple and reliable instrument is needed.
The main advantages
Electromechanical display allowing the user to read the
consumed energy even when the load or the meter is not
power supplied.
direct connection
available.
100A