User guide
3-6 
Stand alone controllers
http://products.ecc.emea.honeywell.com/europe
2
3
4
5
6
7
8
9
10
11
12
13
14
Digital universal input controller with LC-display, pushbuttons, setpoint potentiometer, and 2 control-
outputs.
For space, discharge air humidity control applications, and special applications, e.g. pressure control.
Accessories
Universal input controller, 2 control outputs, Micronik200 
Control output signal 0/2..10V= output and main value deviation signal
Plant output 1 on/off output (24V~) for plant, pump, fan etc.
Control functions PID main (temperature) control, limit control, cascade control, outside 
air compensation control
Main setpoint adjustment built in setpoint potentiometer, or external potentiometer
Parameter settings setpoints, throttling ranges, reset time, summer/winter compensation 
authority, sensor calibration etc.
Analogue input functions 2 inputs for: master and submaster or limit sensor
Applicable sensor types transmitters within the specified input ranges 0..10 V= or 0..20 mA 
Digital input functions plant on/off with external contact or by controller with real time clock
Special input functions compensation temperature sensor, Pt1000, Balco500, NTC20k
Mounting back panel, wall, DIN-rail or front door (with additional mounting 
frame)
Protection class IP30, IP40 (front panel mounting)
Wiring connection screw terminals, max. 1 x 1,5 mm
2
Power supply 24 Vac; 3 VA
Main control range 0 ... 100 %
Housing (HxWxD) 105 mm; 152 mm; 37 mm
Type
R7426D2000
Front panel mounting frame
43193862-001