User guide
25-4
Mechanical Inductive Transmitters
http://products.ecc.emea.honeywell.com/europe
16
17
18
19
20
21
22
23
24
25
26
27
28
16
Mechanical Inductive Transmitters
Pressure transmitter, 3-wire system.
For pressure control of liquids or gaseous media, e.g. for district heating or cooling.
Pressure transmitter with terminal connection for liquid, gas (FNED1)
Kind of pressure overpressure, relative
Pressure connection internal thread G1/4, external thread G1/2
Electrical connection terminal connection 2 x M16x1,5
Protection class IP65
Sensing method mechanical-inductive
Sensing element material 1.4104 + 1.4571
Media temp. 0 ... 70
o
C
Media temp. limit temperatures up to 85
o
C are allowable for short periods. Higher
temperatures are possible, provided that the limit is safeguarded
by suitable measures (e.g. water tube trap, see Accessories for
Pressure Switches / Transmitters)
Medium liquid/gaseous
Ambient temperature 0 ... 45
o
C
Power supply 19..29Vac, 24..36Vdc
Output signal 0/2..10Vdc + 0/4..20mA
Additional description Accuracy class: 1,0
Pressure range Max. pressure
Type
bar bar
0 ... 0,05 2,5
FN505+ED1
0 ... 0,1 5
FN510+ED1
0 ... 0,25 6
FN025+ED1
0 ... 0,5 6
FN05+ED1
0 ... 1 6
FN1+ED1
0 ... 2,5 16
FN3+ED1
Syphons for high temperature, steel, u-shape (for more accessories see Accessories
for Pressure Switches / Transmitters)
U430B