User guide
24-20 
Pressure Switches, component tested
http://products.ecc.emea.honeywell.com/europe
16
17
18
19
20
21
22
23
24
25
26
27
28
16
For maximum-pressure detection of steam, hot water, burnable gases, liquid fuels.
Maximum pressure limiter for hot water, steam, fuel, gas (DWR-B) 
Kind of pressure overpressure, relative
Pressure connection internal thread G1/4, external thread G1/2
Electrical connection Plug DIN 43650
Protection class IP54
Housing material rugged housing of seawater resistant aluminium die casting GD Al Si 
12
Sensing element material 1.4104 + 1.4571
Media temp. -25 ... 70
o
C
Media temp. limit temperatures up to 85 
o
C are allowable for short periods. Higher 
temperatures are possible, provided that the limit is safeguarded by 
suitable measures (e.g. water tube trap, see Accessories for Pressure 
Switches / Transmitters)
Ambient temperature -25 ... 70
o
C
Ambient temp. limit at temperatures below 0 
o
C, ensure that no water condensation can 
arise in the sensor and in the switching device
Switch function/capacity SPDT Microswitch 250 Vac; capacity 5 A inductive, 8 A resistive
Certificates • ID 0000007042 according VdTUEV Memorandum Pressure 100/1, 
Issue 4.83
• TUEV.SDB.02-310 according VdTUEV Memorandum Pressure 
100/1, issue 4.83
• NG-4347AQ1411 according DIN 3398, part 3, issue 11.92
• 3C028/5 according to DIN 3398, Part 4, Issue 10.86
• CE0035BN0004 according Directive 97/23/EC (Module B + D)
• SIL2 according IEC 61508
Pressure interlock/Reset maximum press./button
Pressure adjustment range Max. pressure Allowable max. gas-pressure
(DIN3398P3)
Type
bar bar bar
0,1 ... 0,6 6 6
DWR06-205
0,2 ... 1,6 6 6
DWR1-205
0,2 ... 2,5 16 10
DWR3-205
0,5 ... 6 16 10
DWR6-205
0,5 ... 6 25 20
DWR625-205
3 ... 16 25 20
DWR16-205
4 ... 25 63 50
DWR25-205
8 ... 40 63 50
DWR40-205
Syphon for high temperature, steel, U-shape, for more accessories, see Accessories 
for Pressure Switches / Transmitters)
U430B