User guide

24-15
Pressure Switches, component tested
16
17
18
19
20
21
22
24
23
25
26
27
28
Pressure Switches, component tested
For overpressure monitoring of fuel gases.
Fixed pressure hysteresis
Pressure monitor for fuel gases (DGM)
Kind of pressure overpressure, relative
Pressure connection internal thread G1/4, external thread G1/2
Electrical connection Plug DIN 43650
Protection class IP54
Housing material rugged housing of seawater resistant aluminium die casting GD Al Si
12
Media temp. -25 ... 60
o
C
Media temp. limit temperatures up to 85
o
C are allowable for short periods. Higher
temperatures are possible, provided that the limit is safeguarded by
suitable measures (e.g. water tube trap, see Accessories for Pressure
Switches / Transmitters)
Ambient temperature -25 ... 60
o
C
Ambient temp. limit at temperatures below 0
o
C, ensure that no water condensation can
arise in the sensor and in the switching device
Switch function/capacity SPDT Microswitch 250 Vac; capacity 5 A inductive, 8 A resistive
Optional functions add the type numbers below to the listed type numbers for extra
functionality as described
-213: gold-plated contacts, switching capacity: max. 24 Vdc, 100
mA, min. 5 Vdc, 2 mA. And others not available with adjustable
switching difference.
-301: terminal connection housing, IP65
-513: Gold-plated contacts, single-pole switch-over. Switching
differential permanent. IP65. Switching capacity: max. 24 Vdc, 100
mA, min. 5 Vdc, 2 mA; suitable isolating switching amplifier,
degree of protection EEx-i
-574: Normally closed contact with resistance combination for
minimum pressure monitoring. Gold-plated contacts. Housing
with surface protection (chemical version), IP65
-575: Normally closed contact with reclosing lock-out resistance
combination for minimum pressure monitoring. Housing with
surface protection (chemical version), IP65
-576: Normally closed contact with resistance combination for
maximum pressure monitoring. Gold-plated contacts. Housing
with surface protection (chemical version), IP65
-577: Normally closed contact with reclosing lock-out and
resistance combination for maximum pressure monitoring.
Housing with surface protection (chemical version), IP65
Certificates • NG-4346 AP 1011 according DIN 3398, Part 3 and DIN EN 1854
• CE-0085 AQ 1088 according EU/2009/142/EG (30.11.2009) and
DIN EN 1854 (01.07.2006)
• SIL2 according IEC 61508
Pressure adjustment range Switching differential Max. pressure Sensing element material
Type
bar mbar bar
0,015 ... 0,06 6 0,8 Copper + Brass
DGM306A
0,02 ... 0,1 7 0,8 Copper + Brass
DGM310A
0,04 ... 0,25 10 0,8 Copper + Brass
DGM325A
0,1 ... 0,6 25 2 Copper + Brass
DGM06A
0,2 ... 1,6 40 3 Copper + Brass
DGM1A
0,015 ... 0,06 8 5 1.4104 + 1.4571
DGM506
0,04 ... 0,16 12 5 1.4104 + 1.4571
DGM516
0,1 ... 0,25 20 5 1.4104 + 1.4571
DGM525
Syphon for high temperature, steel, U-shape (for more accessories, see Accessories
for Pressure Switches / Transmitters)
U430B