Standard Pressure Switches
For overpressure monitoring of non-aggressive liquids and gaseous media.
Fixed pressure hysteresis
Adjustable pressure hysteresis
Pressure switch for liquid, gas (DCM)
Kind of pressure overpressure, relative
Pressure connection internal thread G1/4, external thread G1/2
Electrical connection Plug DIN 43650
Protection class IP54
Housing material rugged housing of seawater resistant aluminium die casting GD Al Si
12.
Media temp. -25 ... 70
o
C
Media temp. limit temperatures up to 85
o
C are allowable for short periods. Higher
temperatures are possible, provided that the limit is safeguarded by
suitable measures (e.g. water tube trap, see Accessories for Pressure
Switches / Transmitters)
Ambient temperature -25 ... 70
o
C
Ambient temp. limit at temperatures below 0
o
C, ensure that no water condensation can
arise in the sensor and in the switching device
Switch function/capacity SPDT Microswitch 250 Vac; capacity 5 A inductive, 8 A resistive
Optional functions add the type numbers below to the listed type numbers for extra
functionality as described
-301: terminal connection housing, IP65
-307: two microswitches, switching in parallel or in succession,
fixed switching interval, terminal connection case, IP65
-217: two microswitches, 1 plug, switching in succession,
adjustable switching interval
-213: gold-plated contacts, switching capacity: max. 24 Vdc, 100
mA, min. 5 Vdc, 2 mA. And others not available with adjustable
switching difference.
-351: protection class IP65 and switching housing with surface
protection (chemical version)
-513: gold-plated contacts, switching differential permanent, IP65,
switching capacity: max. 24 Vdc, 100 mA, min. 5 Vdc, 2 mA;
suitable isolating switching amplifier, degree of protection EEx-i
Pressure adjustment
range
Adjustable switching
differential
Switching differential Max. pressure Sensing element
material
Type
bar bar bar bar
0,04 ... 0,25 0,03 6 Copper + Brass
DCM025
0,1 ... 0,6 0,04 6 Copper + Brass
DCM06
0,2 ... 1,6 0,04 6 Copper + Brass
DCM1
0,2 ... 2,5 0,1 16 1.4104 + 1.4571
DCM3
0,5 ... 6 0,15 16 1.4104 + 1.4571
DCM6
0,5 ... 6 0,25 25 1.4104 + 1.4571
DCM625
1 ... 10 0,3 25 1.4104 + 1.4571
DCM10
3 ... 16 0,5 25 1.4104 + 1.4571
DCM16
4 ... 25 1 60 1.4104 + 1.4571
DCM25
8 ... 40 1,3 60 1.4104 + 1.4571
DCM40
16 ... 63 2 130 1.4104 + 1.4571
DCM63
0,04 ... 0,25 0,03 6 1.4104 + 1.4571
DNM025
Pressure adjustment
range
Adjustable switching
differential
Switching differential Max. pressure Sensing element
material
Type
bar bar bar bar
0,04 ... 0,25 0,03 ... 0,4 6 Copper + Brass
DCMV025
0,1 ... 0,6 0,04 ... 0,5 6 Copper + Brass
DCMV06
0,2 ... 1,6 0,07 ... 0,55 6 Copper + Brass
DCMV1