User guide

23-4
Standard Thermostats
http://products.ecc.emea.honeywell.com/europe
16
17
18
19
20
21
22
23
24
25
26
27
28
16
Standard Thermostats
Line voltage frost protection thermostat for reheaters in air conditioning systems, and heat exchangers
in cooling systems.
Accessories
Line voltage thermostat for control of heating-, cooling-, and ventilation systems in industrial areas.
Frost protection thermostat with capillary (T69)
Housing material ABS and corrosion protected steel (IP65 Makrolon)
Ambient temperature -15 ... 55
o
C
Switch function/capacity SPDT 24..250 Vac, 15(8)A
Thermostat application frost protection thermostat
Temp. setpoint range -10 ... 12
o
C
Differential fixed 1 K
Additional description For thermostats with capillary lengths 3m and 6m the DBZ-05
package is included.
Temperature element Capillary tube length Mechanical lock/reset Protection class
Type
m
capillary with bulb 1,8 manual IP54
T6950A1000
capillary 3 manual IP54
T6950A1018
capillary 6 manual IP54
T6950A1026
capillary with bulb 1,8 auto IP54
T6951A1009
capillary 3 auto IP54
T6951A1017
capillary 6 auto IP54
T6951A1025
capillary with bulb 1,8 manual IP65
T6960A1008
capillary 3 manual IP65
T6960A1016
capillary 6 manual IP65
T6960A1024
capillary with bulb 1,8 auto IP65
T6961A1007
capillary 3 auto IP65
T6961A1015
capillary 6 auto IP65
T6961A1023
Fastening clamps 5 pieces
DBZ-05
Room thermostat, industrial, 1/2 stages (T6120)
Housing material glass fibre reinforced ABS
Setpoint device knob
Thermostat application room thermostat
Differential fixed 1 K
Additional description T6120B is dual stage, with 2..10 K difference between the stages.
Temp. setpoint range Switch function/capacity Protection class
Type
o
C
0 ... 60 SPDT 250Vac 10A (1,5A) IP54
T6120A1005
-30 ... 30 SPDT 250Vac 15A (8A) IP65
T6120B1003