User guide
1-8
LonWorks Controllers
http://products.ecc.emea.honeywell.com/europe
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Room temperature controller for pressure (in)dependent, single/dual duct, VAV units, with built in
Microbridge air flow sensor, and actuator.
For cool air damper, re-heater/radiator and fan.
Controller with damper actuator for VAV units, Excel 10 Smart
Control output signal 2 triacs (24V~, 25..400mA) configurable for 3-pt, PWM or single/
multistage control for:
• 3-pt actuator or,
• 2-stage reheater or,
• 1-stage reheater + fan, or
• 1 fan
Control functions cooling only, heat/cool change over, cooling/reheat seq. with
constant or modulating reheat airflow, cooling /radiatorheating
seq. with minimum heat, dual duct, dual duct mixed flow, series/
parallel fan
Control functions with 2
controllers
dual duct constant volume, dual duct mixed flow, dual duct no
flow mixing
Modes of operations occupied, standby, unoccupied, open window
Obligatory inputs • 1 analogue input for room temperature sensor NTC20k; or
apply additional XL10 wall-module with build in sensor on
dedicated input terminals
• airflow
Optional inputs • XL10 wall module input (T7460, T7560-series) with
temperature sensor and other functions
• network input for temperature sensor, setpoint adjustment,
bypass and other functions
• 1 analogue input configurable for discharge or supply or room
temperature sensor NTC20k
• network input for open window, occupancy, change over
Stand-alone operation yes
Network operation yes
Bus system LonWorks(R)
LonMark(R) profile 8010
Power supply 24 Vac; 6 VA
Torque 6 Nm
Housing (HxWxD) 142 mm; 103 mm; 76 mm
Protection class IP40 for all mounting directions
Type
W7751H3007
Auxilliary switch kit, with 2 SPDT freely adjustable switches, IP54, cable 1 m
SSW2-1M