User guide

1-6
LonWorks Controllers
http://products.ecc.emea.honeywell.com/europe
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Room temperature controller for induction units, fan coil units without fan, radiators.
For heater and cooler.
Controller for hydronic installations, Excel 10
Heating output signal 2 triacs (24V~, 250mA) configurable for thermal, 3-pt, PWM or
single/multistage control
Cooling output signal 2 triacs (24V~, 250mA) configurable for thermal, 3-pt, PWM or
single/multistage control
Control functions heat only, cool only, heat/cool change over, heat and cool in
sequence; zero energy band
Modes of operations occupied, standby, unoccupied, open window, frost protection,
summer/winter change over
Optional inputs • 1 digital input configurable for: window or occupancy or
movement
• 1 analogue input for room temperature sensor NTC20k; or
apply additional XL10 wall-module with built in sensor on
dedicated input terminals
• XL10 wall module input (T7460, T7560-series) with
temperature sensor and other functions
• network input for temperature sensor, setpoint adjustment,
bypass and other functions
Stand-alone operation yes
Network operation yes
Bus system LonWorks(R)
LonMark(R) profile 8020
Power supply 24Vac; 0,5VA
Type
W7762B1019