User guide
18-23
Pressure Reducing Valves with flanges
16
17
18
19
20
21
22
24
23
25
26
27
28
Pressure reducing valves of this type protect installations against excessive pressure from the supply. 
They can be used for household, industrial or commercial applications within the range of their 
specification. By installing a pressure reducing valve, pressurisation damage is avoided and water 
consumption is reduced. The set pressure is also maintained constant, even when there is wide inlet 
pressure fluctuation. Reduction of the operating pressure and maintaining it at a constant level 
minimizes flow noise in the installation.
With PN 25 flanged connections
Spare Parts
Standard pattern pressure reducing valve with flanged connections, D17P 
Media Water, compressed air and nitrogen in consideration of valid 
standards (e.g. DIN EN 12502)
Body material spherulitic cast iron GGG40
Spring bonnet material metal
Body finishing powder coating
Port connection type flanges
Max. media temperature 70
o
C
Static pressure PN25
Balanced seat design yes
Additional description • Non-rising stem for setting outlet pressure and position 
indicator on spring bonnet (except for DN 200 mm)
• The adjustment spring is not in contact with the potable water
• With outlet pressure gauge
• Powder coated inside and outside - Powder used is 
physiologically and toxicologically safe
DN size Flow capacity Kvs Pressure setpoint range
Type
mm bar
50 28 1,5 ... 8
D17P-50B
65 47 1,5 ... 8
D17P-65B
80 70 1,5 ... 8
D17P-80B
100 110 1,5 ... 8
D17P-100B
150 250 1,5 ... 8
D17P-150B
200 380 1,5 ... 6
D17P-200B
Pressure gauge, 0 - 10 bar
M07M-A10