Pressure Reducing Valves
http://products.ecc.emea.honeywell.com/europe
16
17
18
19
20
21
22
23
24
25
26
27
28
16
Pressure reducing valves of this type protect installations against excessive pressure from the supply.
They can be used for household, industrial or commercial applications within the range of their
specification. By installing a pressure reducing valve, pressurisation damage is avoided and water
consumption is reduced. The set pressure is also maintained constant, even when there is wide inlet
pressure fluctuation. Reduction of the operating pressure and maintaining it at a constant level
minimizes flow noise in the installation.
With threaded male connections, brass filter bowl
Low pressure pattern pressure reducing valve, D06FN
Media Water, compressed air and nitrogen in consideration of valid
standards (e.g. DIN EN 12502)
Body material brass, dezincification resistant
Spring bonnet material synthetic material
Port connection type external threads
Max. media temperature 70
o
C
Static pressure PN25
Integral filter 0,16 mm
Pressure setpoint range 0,5 ... 2 bar
Balanced seat design yes
Additional description Outlet pressure preset to 1.5 bar
• The outlet pressure is set by turning the adjustment knob
• The adjustment spring is not in contact with the potable water
• The valve insert is of high quality synthetic material and can be
fully interchanged
• Easily retrofittable to convert valve to a reverse-rinsing filter
combination
• Can be retrofitted with an inlet non-return valve
Port diameter DN size Flow capacity Kvs
Type
inch mm
1/2 15 2,4
D06FN-1/2B
3/4 20 3,1
D06FN-3/4B
1257,6
D06FN-1B
1 1/4 32 9,1
D06FN-11/4B
1 1/2 40 12,6
D06FN-11/2B
25012
D06FN-2B