The EA122 air vent is a reliable automatic venting device and is suitable for venting air or gas from 
heating systems or heat process installations.
For hot water heating systems, radiators, wall- and ceiling-mounted air heaters, air collection vessels, 
pipework circuits, boilers and air separators.
Service parts
The sludge and air separator serves to separate sludge and air from the heating system. It is equipped 
with a sludge and contamination reduction feature that functions according to the cyclone principle.
This guarantees an effective separation of the particles. There is an optional phosphate cartridge 
available to prevent corrosion in aluminium-free heating systems.
Standard version
Accessories
Spare Parts
EA122 Automatic air vent with integrated shut-off and leak protection 
Materials Brass connections, high-grade plastic float, float housing and lid, 
heat-resistant elastomer seal components
Medium type water or water-glycol mixture according to VDI 2035
Max. media temperature 110
o
C
Static pressure PN6
Port connection type external threads
Additional description • Integrated shut-off facility.
• Expanding discs to prevent leakage.
• Integrated vacuum break.
• Cleaning and replacement of seal and inner components can 
be carried out without draining the system.
Product description
Type
Connection sizes R 1/8 and R 3/8
EA122-AA
Connection sizes R 1/4 and R 3/4
EA122-BA
Lid with float
0900577
Leak protection discs (pack of 5)
0900761
Sludge and Air Separator, HF49 
Body material brass, dezincification resistant
DN size 25 mm
Max. media temperature 90
o
C
Max. pressure 10 kPa
Nominal flow 3600 kg/h
Kvs value 7,8
Additional description The sludge and air separator is installed in the heating circuit (feed 
and return line) and serves to separate sludge and air from the 
heater water.
Type
HF49-1A
Phosphate cartridge for protection of the heater system against corrosion. Use only 
in heater systems without aluminium materials.
PE49
Venting insert
EE49
Ball valve