User guide

11-13
Room thermostats
2
3
4
5
6
7
8
10
9
11
12
13
14
Wall mounted low voltage room thermostat, with gold-plated contacts and series 18 ohm anticipator.
For low voltage control of zone valves, circulation pumps, boilers, etc.
Accessories
Room thermostat 24Vac with SPST output, T8360
Approvals CE
Protection class IP30
Switch function/capacity SPST 24Vac, 88..127 mA with series anticipator connected
Terminal max. wire size 4 mm
2
Temp. setpoint range 10 ... 30
o
C
Differential fixed 1
o
C
Temperature element vapour filled
Temp. element place built in
Heat anticipator yes
Heating /Cooling
application
Heating only
Product literature
language
Multilingual
Earthing double insulated
Housing (HxWxD) 83 mm; 83 mm; 40 mm
Additional description Switch rating of 10..500 mA if series anticipator is not connected,
by wiring input to terminal 1.
Type
T8360A1000
Range stops, to limit setpoint adjustment (20 pieces)
F42006646 001
Opaque tamperproof cover to prevent thermostat from damage
F42007110 001
Transparent tamperproof cover to prevent thermostat from damage
F42007110 002
Wall-plate to allow mounting onto different wall-boxes
F42007789 001