User guide
11-12 
Room thermostats
http://products.ecc.emea.honeywell.com/europe
2
3
4
5
6
7
8
9
10
11
12
13
14
Wall mounted line voltage room thermostat.
For general purpose control of gas valves, zone valves, circulation pumps, ventilators, boilers etc. in 
heating or cooling systems.
Accessories
Room thermostat 230 Vac, with SPDT output, T6360 
Approvals CE
Protection class IP30
Switch function/capacity SPDT 230 Vac, heating terminal 10 A resistive, 3 A inductive; 
cooling terminal 6 A resistive, 2 A inductive
Terminal max. wire size 4 mm
2
Temp. setpoint range 10 ... 30
o
C
Differential fixed 1
o
C
Temperature element vapour filled
Temp. element place built in
Heating /Cooling 
application
H or C
Earthing double insulated
Housing (HxWxD) 83 mm; 83 mm; 40 mm
Additional description Lamp is generally supplied potential free, and can be wired to 
indicate heating or cooling operation, or boiler lockout.
Heat anticipator Manual operation
functions
Lamp function Temperature
scale
Tamperproof
cover
Product literature
language
Type
–––––Multilingual
T6360A1004
– – wiring dependent – – Multilingual
T6360A1012
•––––Multilingual
T6360B1002
• – wiring dependent – – Multilingual
T6360B1010
•––––English
T6360B1028
• – heating on – – English
T6360B1036
•–––yesEnglish
T6360B1069
•––1..5–English
T6360B1085
•–––yesMultilingual
T6360B1093
•–––suppliedEnglish
T6360B1168
– on/off switch – – – Multilingual
T6360C1000
– on/off switch wiring dependent – – Multilingual
T6360C1018
Range stops, to limit setpoint adjustment (20 pieces)
F42006646 001
Opaque tamperproof cover to prevent thermostat from damage
F42007110 001
Transparent tamperproof cover to prevent thermostat from damage
F42007110 002
Wall-plate to allow mounting onto different wall-boxes
F42007789 001