User guide

8-38
Air quality sensors
http://products.ecc.emea.honeywell.com/europe
2
3
4
5
6
7
8
9
10
11
12
13
14
Air quality sensors
For detection of unpleasant odours, tobacco smoke, and vapours emitted by such materials as
furniture, carpets, paint, glue, etc.
For sensing or controlling of CO
2
concentration in buildings.
For sensing or controlling of CO
2
concentration; and temperature measurement in buildings.
Air quality sensor
Protection class III as per EN60730-1I IP30 as per EN60529
Output signal 0..10Vdc
Power supply 24 Vacdc; 1 VA
Mounting place internal wall
Housing (HxWxD) 104 mm; 99 mm; 30 mm
Additional description Adjustable output offset and LED display
Type
C7110A1010
Room CO2 sensor
LED functions operation as CO
2
indicator
Output signal the following CO
2
output signals are applicable, analog or digital
• 0..10V for 0..2000 ppm (factory setting)
• 0..10 V or 2..10 V for 0..2000 ppm or 0..3000 ppm
(configurable)
• digital output with adjustable CO
2
setpoint and hysteresis for
ventilation on/off
Power supply 24 Vac; 2 VA
Mounting place internal wall
Housing (HxWxD) 104 mm; 99 mm; 30 mm
Wiring terminals 3
Type
C7110C1001
PC interface cable (PC software on request from Honeywell)
HDI10
Room temperature/ CO2 sensor
LED functions operation as occupancy indicator
Output signal the following CO
2
output signals are applicable, analog or digital
• 0..10V for 0..2000 ppm (factory setting)
• 0..10 V or 2..10 V for 0..2000 ppm or 0..3000 ppm
(configurable)
• digital output with adjustable CO
2
setpoint and hysteresis for
ventilation on/off
Temperature element NTC20k
Temperature range 10 ... 35
o
C
Setpoint knob -5 ... 5
o
C
Extra setp. knob 12 ... 30
o
C
Occupancy switch auto/bypass