User guide
8-18 
R.H. ( + temperature) sensors
http://products.ecc.emea.honeywell.com/europe
2
3
4
5
6
7
8
9
10
11
12
13
14
Outdoor R.H.- and temperature sensor 
Protection class IP33
Temperature range -30 ... 50
o
C
R.H. range 5 ... 95 %rh
R.H. sensing element capacitive
R.H. output signal 0..1/10V=
Power supply 24 Vac; 0,48 VA
Mounting place wall outside
Housing (HxWxD) 172 mm; 132 mm; 60 mm
Wiring terminals 6
Temperature element
Type
Balco500
H7508A1034
Pt1000
H7508A1026
NTC20k
H7508A1042
Air duct R.H.- and temperature sensor 
Protection class IP54
R.H. range 5 ... 95 %rh
R.H. sensing element capacitive
R.H. output signal 0..1/10V=
Power supply 24 Vac; 0,48 VA
Mounting place air duct
Immersion depth 235 mm
Temperature element Temperature range Wiring terminals
Type
o
C
––5
H7015A1006
Balco500 -30 ... 70 7
H7015B1012
Pt1000 -30 ... 70 7
H7015B1004
NTC20k -30 ... 70 7
H7015B1020