User guide

5-34
3-way linear valves, stroke 20/38mm
http://products.ecc.emea.honeywell.com/europe
2
3
4
5
6
7
8
9
10
11
12
13
14
For heating and air conditioning; hot/cold water quality VDI2035; greenhouses.
20 mm
38 mm, mixing
38 mm, diverting, action to open AB-A: stem up
Three-way control valve PN16, flanged connections DN 15-150, V5329A/V5050A,B
Valve series V5329A/V5050
Medium type water
Materials body cast iron GG25, trim stainless steel
Action to open stem down
Static pressure PN16
Port connection type flanges ISO7005
Valve type DN size Kvs
value
Close off pressure
with 600N motor
Close off pressure
with 1800N motor
Stroke Media temp. Flow char.
Type
mm kPa kPa mm
o
C
3-way mixing 15 2,5 1000 20 2 ... 170 mod.equal%
V5329A1004
3-way mixing 15 4 1000 20 2 ... 170 mod.equal%
V5329A1012
3-way mixing 20 6,3 1000 20 2 ... 170 mod.equal%
V5329A1020
3-way mixing 25 10 1000 20 2 ... 170 mod.equal%
V5329A1038
3-way mixing 32 16 790 1000 20 2 ... 170 mod.equal%
V5329A1046
3-way mixing 40 25 480 1000 20 2 ... 170 mod.equal%
V5329A1053
3-way mixing 50 40 260 1000 20 2 ... 170 mod.equal%
V5329A1061
3-way mixing 65 63 160 650 20 2 ... 170 mod.equal%
V5329A1079
3-way mixing 80 100 100 400 20 2 ... 170 mod.equal%
V5329A1087
Valve type DN size Kvs
value
Close off pressure
with 600N motor
Close off pressure
with 1800N motor
Stroke Media temp. Flow char.
Type
mm kPa kPa mm
o
C
3-way mixing 100 160 230 38 2 ... 220 linear
V5050A1090
3-way mixing 125 250 90 38 2 ... 220 linear
V5050A1108
3-way mixing 150 360 90 38 2 ... 220 linear
V5050A1116
Valve type DN size Kvs
value
Close off pressure
with 600N motor
Close off pressure
with 1800N motor
Stroke Media temp. Flow char.
Type
mm kPa kPa mm
o
C
3-way
diverting
100 160 230 38 2 ... 220 linear
V5050B1064
3-way
diverting
125 250 90 38 2 ... 220 linear
V5050B1072
3-way
diverting
150 360 90 38 2 ... 220 linear
V5050B1080