Datasheet

Specifications are subject to change without notice (02.10.2003) 3
RM1C
Thermal Specifications
Operating temperature range -30° to +80°C
Storage temperature range -40° to +100°C
Junction temperature < 125°C
Weight Approx. 60 g
Housing material Noryl GFN 1, black
Baseplate Aluminium
Relay
Mounting screws M5
Mounting torque 1.5-2.0 Nm
Control terminal
Mounting screws M3 x 9
Mounting torque 0.5 Nm
Power terminal
Mounting screws M5 x 9
Mounting torque 2.4 Nm
Housing Specifications
Rated insulation voltage
Input to output 4000 VACrms
Output to case 4000 VACrms
Insulation
Carlo Gavazzi Heatsink Thermal ...for power
(see Accessories) resistance... dissipation
No heatsink required --- N/A
RHS 300 5.00 K/W > 0 W
RHS 100 3.00 K/W > 25 W
RHS 45A 2.70 K/W > 60 W
RHS 45B 2.00 K/W > 60 W
RHS 90 1.35 K/W > 60 W
RHS 45A plus fan 1.25 K/W > 0 W
RHS 45B plus fan 1.20 K/W > 0 W
RHS 112 1.10 K/W > 100 W
RHS 301 0.80 K/W > 70 W
RHS 90 plus fan 0.45 K/W > 0 W
RHS 112 plus fan 0.40 K/W > 0 W
RHS 301 plus fan 0.25 K/W > 0 W
Consult your distribution > 0.25 K/W N/A
Infinite heatsink - No solution
--- N/A
Heatsink Selection Applications
Timing
Initial turn-on
The line voltage must be pre-
sent at least 1 period before
the input voltage is applied.
Repetitive turn-on
The input voltage must be
lower than the drop out volt-
age limit at least 1 period be-
fore it is reapplied.
As transformers can have va-
rying stray inductances and
stray capacitances, it is al-
ways advisable to use external
overvoltage protection.
Varistor diameter: 20 mm
Varistor voltage for 400 V SSR:
460 VAC (RV 02)
Varistor voltage for 600V SSR:
680 VAC (RV 05)
Overvoltage protection
Input
voltage
Load
Supply
voltage
Line voltage
Output voltage
Input voltage
Min. 1 period
Input voltage
Min. 1 period
Dimensions