Datasheet
6 Specifications are subject to change without notice (30.01.2018)
Filtering - IEC/EN 55011 Class A compliance (for class B compliance contact us)
Part Number Suggested filter for compliance Maximum Heater current
RGS1.23..25 100 nF / 275 V / X1 25 A
RGS1.23..50 220 nF / 275 V / X1 30 A
330 nF / 275 V / X1 35 A
RGS1.60..25 150 nF / 760 V / X1 25 A
220 nF / 760 V / X1 30 A
RGS1.60..50 330 nF / 760 V / X1 30 A
RGS1.60..51 220 nF / 760 V / X1 30 A
RGS1.60..75 220 nF / 760 V / X1 30 A
330 nF / 760 V / X1 45 A
RGS1.60..90/91/92 220 nF / 760 V / X1 30 A
330 nF / 760 V / X1 45 A
680 nF / 760 V / X1 65 A
EMC Immunity EN 60947-4-3
Electrostatic Discharge (ESD)
Immunity IEC/EN 61000-4-2
Air discharge, 8kV Performance Criteria 1
Contact, 4kV Performance Criteria 1
Electrical Fast Transient
(Burst) Immunity IEC/EN 61000-4-4
Output: 2kV, 5kHz Performance Criteria 1
Input: 1kV, 5kHz Performance Criteria 1
Electrical Surge Immunity
9
IEC/EN 61000-4-5
Output, line to line, 1kV Performance Criteria 1
Output, line to earth, 2kV Performance Criteria 1
Input, line to line, 1kV Performance Criteria 2
Input, line to earth, 2kV Performance Criteria 2
Radiated Radio Frequency
Immunity IEC/EN 61000-4-3
10V/m, 80 - 1000 MHz Performance Criteria 1
10V/m, 1.4 - 2.0GHz Performance Criteria 1
3 V/m, 2.0 - 2.7GHz Performance Criteria 1
Conducted Radio Frequency IEC/EN 61000-4-6
Immunity
10V/m, 0.15 - 80 MHz Performance Criteria 1
Voltage Dips Immunity IEC/EN 61000-4-11
0% for 0.5, 1 cycle Performance Criteria 2
40% for 10 cycles Performance Criteria 2
70% for 25 cycles Performance Criteria 2
80% for 250 cycles Performance Criteria 2
Voltage Interruptions Immunity IEC/EN 61000-4-11
0% for 5000ms Performance Criteria 2
EMC Emission EN 60947-4-3
Radio Interference
Voltage Emission (Conducted) IEC/EN 55011
0.15 - 30MHz Class A (industrial) with filters
- see filter information
Radio Interference
Field Emission (Radiated) IEC/EN 55011
30 - 1000MHz Class A (industrial)
Electromagnetic Compatibility
RGS..E, RGS..EDIN
Note:
• Control input lines must be installed together to maintain products’ susceptability to Radio Frequency interference.Use of AC solid state relays
may, according to the application and the load current, cause conducted radio interferences. Use of mains filters may be necessary for cases
where the user must meet E.M.C requirements. The capacitor values given inside the filtering specification tables should be taken only as indica-
tions, the filter attenuation will depend on the final application.
• Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
• Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However when the test is complete the
product should return operating as intended by itself.
• Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.
9: An external varistor, S20K750, needs to be connected across the mains supply for the RGS1A69.. models