Datasheet

7 Overload profile for AC-53a;
Ie: AC-53a: x-Tx: F-S, where Ie = nominal current (AC-53a AAC), x = overload current factor, Tx = duration of overload current (s), F = duty cycle (%), S = number of starts per hour. Example;
5A: AC-53a: 6 - 6 : 50 - 30 = max. 30 starts for the RGS..25 with an overload profile of 30A for 6 seconds with a duty cycle of 50%
4 Specifications are subject to change without notice (30.01.2018)
RGS..E, RGS..EDIN
Motor Ratings
6
: HP (UL 508) / kW (EN/IEC 60947-4-2) @ 40
0
C
Output Specifications
Output Specifications for RGS..DIN
RGS..25..DIN RGS..50..DIN RGS..90..DIN
Rated operational current
8
AC-51 rating @ Ta = 40˚C 10 AAC 12 AAC 12 AAC
AC-53a rating @ Ta =40˚C 5 AAC 5 AAC 5 AAC
Number of motor starts per hour (x:6, Tx:6s, F:50%)
at 40˚C
7
30 30 30
Min. operational current 150 mA 250 mA 400 mA
Maximum transient surge current I
TSM
, t=10ms 325 Ap 600 Ap 1150 Ap
Maximum off-state leakage current @ rated voltage 3 mAAC 3 mAAC 3 mAAC
I²t for fusing (t=10ms), Minimum 525 A
2
s 1800 A
2
s 6600 A
2
s
Crititcal dv/dt (@ Tj init = 40˚C) 1000 V/us 1000 V/us 1000 V/us
8: Refer to Derating Curves for RGS...DIN
115 VAC 230 VAC 400 VAC 480 VAC 600 VAC 690 VAC
RGS..25 ½HP / 0.18kW 1½HP / 0.37kW 3HP / 0.75kW 3HP / 1.1kW 5HP / 1.5kW - / 1.5kW
RGS..50/51 1HP / 0.37kW 3HP / 1.1kW 5HP / 1.5kW 5HP / 2.2kW 7½HP / 3.7kW - / 3.7kW
RGS..75
1½HP / 0.56kW
3HP / 1.5kW 5HP / 3kW 7½HP / 4kW 10HP / 4kW - / 4kW
RGS..90/91/92 2HP / 0.75kW 5HP / 2.2kW 7½HP / 4kW 10HP / 4kW 15HP / 5.5kW - / 5.5kW
6: Refer to Heatsink Selection Table
RGS..25.. RGS..50/51.. RGS..75.. RGS..90/91.. RGS..92..
Rated operational current
AC-51 rating @ Ta=40˚C
(IEC60947-4-3/UL508)
6
25 AAC 50 AAC 75 AAC 90 AAC 90AAC
AC-53a rating @ Ta=40˚C
(IEC60947-4-2/ UL508) 5 AAC 10 AAC 14.8 AAC 18 AAC 18AAC
Number of motor starts per hour
(x:6, Tx:6s, F:50%) at 40˚C
6, 7
30 30 30 30 30
Min. operational current 150 mAAC 250 mAAC 400 mAAC 400 mAAC 500 mAAC
Rep. overload current -
(Motor rating) PF = 0.4-0.5
UL508: T
AMB
=40˚C,
t
ON
=1s, t
OFF
=9s, 50 cycles 67 AAC 107 AAC 126 AAC 168 AAC 168 AAC
Maximum trasient surge current
(I
TSM
), t=10ms 325 Ap 600 Ap 800 Ap 1150 Ap 1900 Ap
Maximum off-state leakage current
@ rated voltage 3 mAAC 3 mAAC 3 mAAC 3 mAAC 3 mAAC
I²t for fusing (t=10ms), Minimum 525 A²s 1800A²s 3200A²s 6600A²s 18000A²s
Crititcal dv/dt (@ Tj init = 40˚C) 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us