Detailed Over temperature Alarm Procedure (for RGC...P)
ALARM Signal onlyALARM Signal and FAN
START
FAN: ON
Is Chip
t
emperature >
115°C ?
N
Y
Chip
temperature <
85°C ?
N
Y
START
N
Y
N
Y
SSR output: OFF
R
ed LED: ON
Alarm Signal: ON
Y
N
Chip
temperature <
80°C?
FAN: OFF
C
hip
temperature
l
imit reached?
SSR output: ON
Red LED: OFF
Alarm Signal: OFF
Chip
temperature
limit reached?
SSR output: OFF
Red LED: ON
Alarm Signal: ON
START
FAN: ON
Is Chip
t
emperature >
115°C ?
N
Y
Chip
temperature <
85°C ?
N
Y
START
N
Y
N
Y
SSR output: OFF
R
ed LED: ON
Alarm Signal: ON
Y
N
Y
Chip
temperature <
80°C?
N
SSR output: ON
Red LED: OFF
Alarm Signal: OFF
FAN: OFF
FAN: OFF
C
hip
temperature
l
imit reached?
SSR output: ON
Red LED: OFF
Alarm Signal: OFF
Chip
temperature <
80°C?
Chip
temperature
limit reached?
SSR output: OFF
Red LED: ON
Alarm Signal: ON
CAUTION
Alarm condition resets whenever the voltage signal is removed from terminal A1 (+)
In the case of RGC...D90GGEP, if the voltage signal is not applied across A1(+) and A2 (-) terminals, the overtemperature detection and functionality is lost
(including fan operation and alarm signalling)
In the case of RGC1A60A90GGEP it is necessary to supply IN2 and IN3 with 24VDC for fan operation.
Alarm procedure for RGC1A60A90GGEP follows ‘Alarm signal only’ flow since fan is continously operating.
Alarm condition automatically resets ONLY when power semiconductor temperature < 80˚C
Temperatures indicated are typical figures.
Motor Ratings: HP (UL508) / kW (IEC60947-4-2) @ 40°C
115 VAC 230 VAC 400 VAC 480 VAC 600 VAC
RGC..15
1
/
3
HP / 0.18kW 1HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW
RGC..20 ½HP / 0.18kW 1-½HP / 0.37kW 2HP / 0.75kW 3HP / 1.1kW 3HP / 1.5kW
RGC..30 3/4HP / 0.37kW 2HP / 1.1kW 3HP / 1.5kW 5HP / 2.2kW 5HP / 3.7kW
R
GC..40 1HP / 0.56kW 3HP / 1.5kW 5HP / 2.2kW 5HP / 3.7kW 7-½HP / 4kW
RGC..60 1-½HP / 0.56kW 3HP / 1.5kW 5HP / 3kW 7-½HP / 4kW 10HP / 4kW
R
GC..90GGEP 2HP / 0.75kW 5HP / 1.5kW 7½HP / 4kW 10HP / 4kW 15HP / 5.5kW
A
LARM Signal and Fan
(
applicable to RGC..D90GGEP)
A
LARM Signal only