Protection with Miniature Circuit Breakers
Solid State Relay Model no. for Model no. for Wire cross Minimum length of
type Z - type M. C. B. B - type M. C. B. sectional area [mm
2
] Cu wire conductor [m]
13
(rated current) (rated current)
R
GC..15, RGC..20 S201 - Z4 (4A) S201 - B2 (2A) 1.0 21.0
S201 - Z6 UC (6A) S201 - B2 (2A) 1.0 21.0
1
.5 31.5
RGC..30 S201 - Z10 (10A) S201-B4 (4A) 1.0 7.6
1
.5 11.4
2.5 19.0
S201 - Z16 (16A) S201-B6 (6A) 1.0 5.2
1
.5 7.8
2
.5 13.0
4.0 20.8
S201 - Z20 (20A) S201-B10 (10A) 1.5 12.6
2
.5 21.0
S
201 - Z25 (25A) S201-B13 (13A) 2.5 25.0
4.0 40.0
S202 - Z25 (25A) S202-B13 (13A) 2.5 19.0
4
.0 30.4
RGC..40 S201 - Z25 (25A) S201-B13 (13A) 2.5 7.0
4
.0 11.2
6.0 16.8
RGC..60 S201 - Z25 (25A) S201-B13 (13A) 2.5 7.0
4.0 11.2
6.0 16.8
RGC..90GGEP S201 - Z20 (20A) S201-B10 (10A) 1.5 4.2
2.5 7.0
4.0 11.2
S202 - Z20 (20A) S202-B10 (10A) 1.5 1.8
2.5 3.0
4.0 4.8
S201 - Z32 (32A) S201-B16 (16A) 2.5 13.0
4.0 20.8
6.0 31.2
S202 - Z32 (32A) S202-B16 (16A) 2.5 5.0
4.0 8.0
6.0 12.0
10.0 20.0
S202 - Z50 (50A) S202-B25 (25A) 4.0 14.8
6.0 22.2
10.0 37.0
13. between MCB and SSR Relay (including return path which goes back to the mains).
Note: A prospective current of 6kA and a 230/400V power supply system is assumed for the above suggested specifications. For cables with different cross
section than those mentioned above please consult Carlo Gavazzi's Technical Support Group.