Datasheet

POWER CONNECTIONS: 1/L1, 2 /T1
U
se 75°C copper (Cu) conductors
RGC..15.KE. ; RGC..20.KE. ; RGC..30.KE. RGC..40.GE. ; RGC..60.GE. ; RGC..90GGEP
Stripping Length (X) 12mm 11mm
Connection type M4 screw with captivated washer M5 screw with box clamp
Rigid (Solid & Stranded)
UL/ cUL rated data
2 x 2.5..6 mm
2
1 x 2.5..6 mm
2
1 x 6..25mm
2
2 x 14.. 10 AWG 1 x 14.. 10 AWG 1 x 10...3 AWG
Flexible with end sleeve 2 x 1.0 ... 2.5mm
2
2 x 2.5..4mm
2
1 x 1.0..4mm
2
1 x 2.5..16mm
2
2 x 18.. 14 AWG 1 x 18.. 12 AWG 1 x 14.. 6 AWG
2 x 14.. 12 AWG
Flexible without 2 x 1.0 ... 2.5mm
2
end sleeve 2 x 2.5.. 6mm
2
1 x 1.0.. 6mm
2
1 x 4.. 25mm
2
2 x 18.. 14 AWG 1 x 18.. 10 AWG 1 x 12.. 3 AWG
2 x 14.. 10 AWG
Torque specifications 2 Nm (17.7 in-lb). 2.5 Nm (22 in-lb).
M4, Pozidriv 2 M5, Pozidriv 2
Aperture for termination lug 12.3mm N/A
Protective Earth Connection
RGC..15, 20: M4, 1.5Nm (13.3 in-lb)
RGC..30, 40, 60, 90: M5, 1.5Nm (13.3 in-lb)
Note: Protective Earth connection must be connected whenever the product is intended to be used in Class 1 applications according to EN/IEC 61140.
Connection Specifications
X
CONTROL CONNECTIONS: A1(+), A2(-), IN1, IN2, IN3, 11 (+), 12(-), OUT
Use 60/75°C copper (Cu) conductors RGC...GGEP
Torque specifications 0.5 Nm (4.4 in-lb); M3, Pozidriv 1
Stripping Length (X) 6mm 13mm
Rigid (Solid & Stranded)
UL/ cUL rated data
2 x 0.5..2.5mm
2
1 x 0.2..2.5mm
2
2 x 18..12 AWG 1 x 24..12 AWG
Flexible with end sleeve
2 x 0.5..2.5mm
2
1 x 0.2..2.5mm
2
2 x 18..12AWG 1 x 24..12AWG
X
CONTROL CONNECTIONS: A1(+), A2(-)
Use 60/75°C copper (Cu) conductors
RGC..K.E RGC....M.E
Torque specifications 0.5 Nm (4.4 in-lb); M3, Pozidriv 1
Stripping Length (X) 8mm 12 - 13mm
Rigid (Solid & Stranded)
UL/ cUL rated data
2 x 0.5..2.5mm
2
1 x 0.5..2.5mm
2
1 x 0.2...2.5mm
2
2 x 18..12 AWG 1 x 18..12 AWG 1 x 24...12 AWG
Flexible with end sleeve
2 x 0.5..2.5mm
2
1 x 0.5..2.5mm
2
2 x 18..12AWG 1 x 18..12AWG
X
18 Specifications are subject to change without notice (30.06.2011)