Datasheet

Specifications are subject to change without notice (30.06.2011) 3
RGC...E
Output specifications (@ 25°C unless otherwise specified)
R
GC..15.. RGC..20.. RGC..30.. RGC..40.. RGC..60.. RGC..90..
Rated operational current
6
AC-51 rating @ Ta=25°C 20 AAC 25.5 AAC 30 AAC 47.4 AAC 70.4 AAC 85 AAC
AC-51 rating @ Ta=40°C 20 AAC 23 AAC 30 AAC 40 AAC 60 AAC 85 AAC
AC-53a rating @ Ta=40°C 5 AAC 5 AAC 8 AAC 13 AAC 14.8 AAC 18 AAC
Number of motor starts
(x:6, Tx:6s, F:50%) at 40˚C
5
30 30 30 30 30 30
Min. operational current 150 mAAC 150 mAAC 250 mAAC 400 mAAC 400 mAAC 400 mAAC
Rep. overload current -
(Motor Rating) PF = 0.4 - 0.5
UL508: T
A
MB
=4C, t
O
N
=1s, t
O
FF
=9s,
50cycles 60 AAC 60 AAC 84 AAC 126 AAC 144 AAC 168 AAC
Maximum transient surge current (I
T
SM
) 325 Ap 325 Ap 600 Ap 800Ap 800Ap 1150Ap
Maximum off-state leakage current 3 mA 3 mA 3 mA 3 mA 3 mA 3 mA
t (10ms) Minimum 525 A²s 525 A²s 1800 s 3200A²s 3200A²s 6600A²s
Crititcal dv/dt (@ Tj init = 25°C) 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us 1000 V/us
5. Overload current profle definition: x: multiple of AC53a rating, Tx: duration of current surge, F: duty cycle
6
. See derating curves
7: DC supply for alarm signal should be supplied from a Class 2 power source
8: Maximum voltage to be applied between 11+ and 12- (Ua) terminals should be 35VDC maximum with reference to A2-
Overtemperature alarm specifications for RGC...P
RGC..D..P RGC..A..P
Output type PNP open collector Potential Free
Normal state Closed Closed
Maximum current rating 50 mADC 50 mADC
Rated voltage (EN61131-2: 2003)
8,7
, Ua 24VDC -15%, +20% 24VDC -15%, +20%
Rated voltage, Us RGC...D90GGEP 24VDC ± 10% N/A
Fan rating, Uf RGC...A90GGEP N/A 24VDC ±10%, 50mA nominal
Alarm voltage drop Typical 2.8VDC 1.8VDC
Maximum 4VDC 3.5VDC
Visual Indication Continous Red LED Continous Red LED
Reverse polarity protection 24VDC 24VDC