Datasheet

4 Specifications are subject to change without notice (28.11.2017)
RAM..G
Immunity EN60947-4-3
Electrostatic Discharge (ESD)
Immunity IEC/EN 61000-4-2
Air discharge, 8 kV Performance Criteria 2
Contact, 4 kV Performance Criteria 2
Electrical Fast Transient
(Burst) Immunity IEC/EN 61000-4-4
Output: 2 kV, 5 kHz Performance Criteria 1
Input: 1 kV, 5 kHz Performance Criteria 1
Electrical Surge Immunity IEC/EN 61000-4-5
Output, line to line, 2 kV Performance Criteria 2
Output, line to earth, 2 kV Performance Criteria 2
Input, line to line, 1 kV
Performance Criteria 2
Input, line to earth, 2 kV Performance Criteria 2
Radiated Radio Frequency Immunity IEC/EN 61000-4-3
10 V/m, 80 - 1000 MHz Performance Criteria 1
10 V/m, 1.4 - 2.0 GHz Performance Criteria 1
3 V/m, 2.0 - 2.7 GHz Performance Criteria 1
Conducted Radio Frequency IEC/EN 61000-4-6
Immunity
10 V/m, 0.15 - 80 MHz Performance Criteria 1
Voltage Dips Immunity IEC/EN 61000-4-11
0% for 0.5, 1 cycle Performance Criteria 2
40% for 10 cycles Performance Criteria 2
70% for 25 cycles Performance Criteria 2
80% for 250 cycles Performance Criteria 2
Voltage Interruptions Immunity IEC/EN 61000-4-11
0% for 5000 ms Performance Criteria 2
EMC Emission EN60947-4-3
Radio Interference
Voltage Emission (Conducted) IEC/EN 55011
0.15 - 30 MHz Class A (industrial) with filters
IEC/EN 60947-4-3 Class A (no
filtering needed up to 75AAC)
Radio Interference
Field Emission (Radiated) IEC/EN 55011
30 - 1000 MHz Class B
Electromagnetic Compatibility
Notes:
- Control input lines must be installed together to maintain products’ susceptibility to Radio Frequency interference.
- Performance Criteria 1: No degradation of performance or loss of function is allowed when the product is operated as intended.
- Performance Criteria 2: During the test, degradation of performance or partial loss of function is allowed. However, when the test is complete the product should
return operating as intended by itself.
- Performance Criteria 3: Temporary loss of function is allowed, provided the function can be restored by manual operation of the controls.