User manual
UDM 35/40 PANEL METER USER MANUAL
17
Programming example:
Retransmit a 4-20mA signal proportional to the following displayed values:
Lo.D = 0 and Hi.D = 18.
When is displayed, the Analog Output program may be addressed. Press
to enter sequence. is displayed. Press to toggle to the first
position. Use the keys to select value “0”. Press to toggle to the left to
“tens” position. Using keys, select value “2” and press enter to confirm
all choices and advance to the next program sequence.
will be displayed. Press to toggle to “hundreds” position and use
keys to select “1”. Press to toggle to each remaining position and
select “0” for each. When completed, press to confirm and advance to the
next program sequence.
will be displayed. Using the keys choose either “A” for 20mA
output full range, or “U” for 10v output. In this example, the selection would be
“A”. Press to confirm. Press to advance to the next program step
sequence.
Serial Port Output
When is displayed you may elect to configure a serial port address and
baud rate. Press . will be displayed. Using the key, toggle to the
desire position and select the proper value(s) using the
keys. Press to
confirm.
When
is displayed, use the keys to select the desired baud rate
indicated in kbits/sec. Press
to confirm. Press to advance to the next, and
last, program step sequence.