Datasheet
5
Carlo Gavazzi Automation S.p.A.
ICS08 IO-Link 3-wire DC
ICS08 IO-Link 3-wire DC DS EN11/05/2018
Sensing
Detection
Rated operating distance S
n
2 mm ush or 4 mm non-ush
Reference target
The operating distance is measured according to IEC 60947-5-2, using a
standard target moving axially.
This target is square shape 1 mm thickness, made of steel e.g. type Fe 360
as dened in ISO 630 and it shall be of the rolled nish.
The length of the side of the square is equal to
– the diameter of the circle inscribed on the active surface of the sensing face,
or
– three times the rated operating distance S
n
whichever is greater
Assured operating sensing distance
(S
a
)
0 ≤ S
a
≤ 0.81 x S
n
(e.g. with S
n
of 2 mm, S
a
is 0 ... 1.62 mm)
Eective operating distance (S
r
) 0.9 x S
n
≤ S
r
≤ 1.1 x S
n
Usable operating distance (S
u
) 0.9 x S
r
≤ S
u
≤ 1.1 x S
r
Temperature drift ≤ +/-10%
Hysteresis (H) 1...20%
Y
X
S
T
S: sensor
T: target
-4 4122028364452606876
-197
-131,3
-65,7
0
65,6
131,3
197
-4
-2
0
2
4
00,2 0,40,6 0,81 1,21,4 1,61,8 2
Distance [Thou]
[Thou]
[mm]
Distance [mm]
S
T
-19,70 19,7 39,4 59,1 78,8 98,5 118,2137,9 157,6
-276
-207
-138
-69
0
69
138
207
276
-6
-4
-2
0
2
4
6
-0,5 00,5 11,5 22,5 33,5 4
Distance [Thou]
[Thou]
[mm]
Distance[mm]
S
T
Fig. 1 Flush Fig. 2 Non-ush
Sensors with IO-Link communication
Rated operating distance S
n
Programmable via IO-Link: 50% or 100% of the maximum S
n
Hysteresis (H) Programmable via IO-Link: standard or increased
Correction factors
The specic operating distance S
n
refers to dened measuring conditions. The following data have to be
considered as general guidelines.