Parameter Description
Multiplexer
(Detection of counter
values)
Counter range With this setting made under <Edit><Counter And Mux Analog Setup>, you
select the range of counter values. Depending on the range, a coresponding
number of channel groups, beginning by “B” are reserved:
Counter ranges Reserved groups
--- None (counter operation switched off)
0..99 B..C
0..9999 B..D
0..999999 B..E
0..99999999 B..F
Parameters
Object Function Channel
In-/outputs
Counter input Detection of B1..F8
impulses from
energy counter
Relay output Switching power G1..N8
outlets
Configuration of Master Generator
Counter range Channels for B1..F8
counter values
Toggle switch function Switches for power G1..N8
Application Example
Task: On a camping site, 64 current values are to be detected and used on a PC for the issue of
invoices.
Solution: The counter modules G4420 7401 are built into the local power cabinets. Four Dupline energy
counters supply one G4420 7401 with the corresponding impulses. The Master Generator is
configured for Counter setup through entry of the counter ranges. A data entry software avail-
able through a DDE interface reads out the values via the DDEServer and resets the counter
value when a new guest arrives.
The voltage of the individual power outlet is turned on from the PC through a relay module
(software DP-Camp). Free channels are used for this purpose.
The applied Master Generator can, of course, also perform additional automation functions.