Object Function Channel
In-/outputs
Alarm switch Alarm contact A1..A8
Push button input Acknowledgement B1
Push button input Reset B2
Push button input Lamp test B3
Semiconductor output LED for source in- A1..A8
cation on a panel
Relay output Alarm siren B4
Configuration of Master Generator
ISA alarm: Alarm sources A1.. A8
Passive detector
ISA alarm: Alarm B1
Acknowledgement acknowledgement
ISA alarm: Reset Alarm reset B2
ISA alarm: Lamp test Activation of all B3
LEDs on the panel
ISA alarm: Alarm siren Alarm sounding B4
Application Example
Task: In a chemical factory, eight laboratories are to be provided with alarm switches. Upon activation
of an alarm button, the fire staff of the factory is informed via a siren. When the fire staff has
acknowledged the alarm, they go to the lab where the alarm was started.
Solution: The alarm switches are coded for channels A1 to A8. The source of the alarm is indicated on a
panel whose LED is activated via a mimic display. The addresses correspond to those of the
alarm contacts. The fire staff uses a button coded for address B1 to acknowledge the alarms.
The alarm is reset through a reset button coded for address B2. The alarm is sounded by
means of a horn activated through a relay output of DSM 8 coded for address B4.