Datasheet
12 Specifications are subject to change without notice EM24 DIN DS 260315
EM24 DIN
Display pages
S
el.
pos.
No
1st variable (1st
line)
2nd variable (2nd
line)
3rd variable (3rd
line)
Note
Applications
A B C D E F G H I
1 Phase seq. VLN sys Hz 7 7 7 7 7 7 7
2 Phase seq. VLL sys Hz x x x
3 Total kWh (+) W sys dmd W sys dmd max x x x x x x x
4 kWh (+) A dmd max (text) “PArt” “PArt” = Partial kWh (+) x x x
5 Total kvarh (+) VA sys dmd VA sys dmd max 7 7 7 7
6 kvarh (+) VA sys (text) “PArt” “PArt” = Partial kvarh (+) 7 7 7
7 Totalizer 1 (2) W sys (8) (text) (3) (1) x x x x
8 Totalizer 2 (2) W sys (8) (text) (3) (1) x x x x
9 Totalizer 3 (2) W sys (8) (text) (3) (1) x x x x
10 kWh (+) t1 tariff (4) W sys dmd (1) digital input enabled x x x x
11 kWh (+) t2 tariff (4) W sys dmd (1) digital input enabled x x x x
12 kWh (+) t3 tariff (4) W sys dmd (1) digital input enabled 5 5 5 5
13 kWh (+) t4 tariff (4) W sys dmd (1) digital input enebled 5 5 5 5
14 kvarh (+) t1 tariff (4) W sys dmd (1) digital input enabled 7 7 7 7
15 kvarh (+) t2 tariff (4) W sys dmd (1) digital input enabled 7 7 7 7
16 kvarh (+) t3 tariff (4) W sys dmd (1) digital input enabled 5,7 5,7 5,7 5,7
17 kvarh (+) t4 tariff (4) W sys dmd (1) digital input enabled 5,7 5,7 5,7 5,7
18 kWh (+) X W X User X (1) specific function enabled x
19 kWh (+) Y W Y User Y (1) specific function enabled x
20 kWh (+) Z W Z User Z (1) specific function enabled x
21 Total kvarh (-) VA sys dmd VA sys dmd max 7 7
22 Total kWh (-) W sys dmd W sys dmd max x x x
23 Hours W sys PF sys x x x x
24 Hours var sys PF sys 7 7 7 7
25 var L1 var L2 var L3 7 7
26 VA L1 VA L2 VA L3 7 7
27 PF L1 PF L2 PF L3 7 7
28 W L1 W L2 W L3 7 7 7
29 A L1 A L2 A L3 x x x x x
30 V L1-2 V L2-3 V L3-1 6 6 6
31 V L1 V L2 V L3 7 7 7 7 7 7
32 Total kWh (+) W sys x
0 Selector position which can be linked to any of the variable combinations listed above (No. from 1 to 31)
1 Selector position which can be linked to any of the variable combinations listed above (No. from 1 to 31)
2 Selector position which can be linked to any of the variable combinations listed above (No. from 1 to 31)
3
Selector position which can be linked to any of the variable combinations listed above (No. from 1 to 31) In this position the front LED blinks pro-
portionally to the reactive energy (kvarh) being measured
(1) The page is available according to the enabled measurement.
(2) m
3
Gas, m
3
Water, kWh remote heating, external kWh meter. Not available in M-bus version.
(3) Hot and Cold (water), GAS. ENE (external energy meter). Not available in M-bus version.
(4) The active tariff is displayed with an “A” before the “t1-t2-t3-t4” symbols. Not available in M-bus version.
(5) These pages are not available in case of Dupline model.
(6) Pages not available in case of 1-phase system (1P selection).
(7) Pages not available in case of 3-phase unbalanced system (3P selection).
(8) In case of external kWh meter the text “W sys” is replaced by “out”.
Note: in case of alarm the whole display blinks. The blinking stops when either the selector or the joystick are used. The
display starts to blink again after 60 seconds of the last command being used. There is a time-out of 60s that brings the
scrolled page to the default one (selectable according to the table given above).