Datasheet
Specifications are subject to change without notice EM24 DIN DS 220213 7
EM24 DIN
Self supplied version AV9 models
“XX” and “O2” options
only: -20% +15%, 48-
62Hz. “R2”, “XS” and “IS”
options only: -15% +10%,
48-62Hz.
AV2 model:
“XX”, “O2”, “IS” and “DP”
options: -15% +15%, 48-
62Hz. In case of 3-phase
system, 4-wire connection:
113 to 265V. In case of 3-
phase system, 3-wire con-
nection: 196 to 460V.
Note The instruments provided
with “IS” and “R2” options
work only if all the voltage
inputs are connected (3-
phase and neutral) if a 1-
phase connection has to
be performed the L1 and
L2 voltage inputs have to
be short circuited. The
instrument provided with
“O2” option, working in a
3-phase system with neu-
tral may work also if one or
two phases are missing.
Auxiliary power supply AV5-AV6 modules:
L: 18 to 60V
AC/DC;
D: 115VAC/230VAC
(48 to 62Hz)
Power consumption
AV9-AV2 models ≤ 20VA/1W
A
V9-AV2 models
(IS and DP option only) ≤ 12VA/2W
AV5-AV6 models ≤ 2VA/2W
Power supply specifications
Cable cross-section area
A
V5-AV6 models Max. 1.5 mm
2
S
crews tightening torque:
0
.5 Nm
Housing DIN
Dimensions (WxHxD) 71 x 90 x 64.5 mm
Material Nylon PA66,
self-extinguishing: UL 94 V-0
Mounting DIN-rail
Protection degree
Front IP50
Screw terminals IP20
Weight Approx. 400 g (packing
included)
Standard compliance
Safety IEC60664, IEC61010-1
EN60664, EN61010-1
EN62052-11.
Metrology EN62053-23, EN50470-3.
MID ”annex MI-003”
P
ulse output DIN43864, IEC62053-31
A
pprovals CE, cULus listed (AV5, AV6
o
ptions only), MID (PF
option only)
Connections Screw-type
Cable cross-section area
AV2-AV9 models measuring inputs max.
16 mm
2
; min. 2.5 mm
2
(by
cable lug). Min./Max.
screws tightening torque:
1.7 Nm / 3 Nm
Other inputs: 1.5 mm
2
Screws tightening torque:
0.5 Nm
General specifications (cont.)
Output Model Note
Open collector output “AV9” models with “O2” option
The meter works even if up to two voltages “phase
to neutral” are missing or if one voltage “phase to
phase” is missing.
Relay output “AV9” models with “R2” option
The neutral wire has always to be available. The
meter works even if “Phase 3” is missing but,
mandatorily, both “phase 1” and “Phase 2” have to
be available.
RS485 port “A
V9” models with “IS” option
Dupline port “A
V2” model with “DP” option
The meter works even if up to two voltages “phase
to neutral” ar
e missing or if one voltage “phase to
phase” is missing.
Relay output “A
V2” model with “R2” option
RS485 port “A
V2” model with “IS” option
Working mode notes (only “Self power supply” version)