Datasheet
Specifications are subject to change without notice EM24 DIN DS 220213 1
• Class 1 (kWh) according to EN62053-21
• Class B (kWh) according to EN50470-3
• Class 2 (kvarh) according to EN62053-23
• Accuracy ±0.5 RDG (current/voltage)
• Energy analyzer
• Instantaneous variables readout: 4 DGT
• Energies/gas/water readout: 8 DGT
•
System variables: VLL, VLN, Admd max, VA, VAdmd, VAdmd max,
W, Wdmd, Wdmd max, var, PF, Hz, Phase-sequence.
• Single phase variables: VLL, VLN, A, VA, W, var, PF
• Energy measurements: total and partial kWh and kvarh or based on
4 different tariffs; single phase measurements
• Gas, cold water, hot water, kWh
remote heating
measurements
• Hour counter (6+2 DGT)
• TRMS measurements of distorted sine waves (voltages/cur-
rents)
• Self power supply (AV2-AV9 inputs)
• Auxiliary power supply (AV5-AV6 inputs)
•
3 digital inputs for tariff selection, DMD synch or gas/
water (hot-cold) and remote heating metering (on request)
• 2 digital outputs for pulses or for alarms or as a mix of them
• Dimensions: 4-DIN modules
• Protection degree (front): IP50
• RS485 serial output (MODBUS-RTU), iFIX SCADA compatibility
• Dupline communication capability (DP option)
Product Description
Three-phase energy analyzer
with built-in configuration joy-
stick and LCD data displaying;
particularly indicated for active
and reactive energy metering
and for cost allocation. Housing
Energy Management
Energy Analyzer
Type EM24 DIN
• Application adaptable display and programming procedure
(Easyprog function)
• Easy connections management
• Certified according to MID Directive (option PF):
see “how to or
der” below
• Other versions available (not certified, option X):
see “how to order” on the next page
for DIN-rail mounting with IP50
(front) protection degree. Direct
connection up to 65A and by
means of external current and
potential transformers.
Moreover the meter can be
Model
Range code
System
Power supply
Inputs/Outputs
Option
Measur
ement
EM24 DIN AV5 3 D O2 PF A
Type Selection for MID version
Range codes
AV5: 400V
LL
AC - 5(10)A
(CT connection)
AV2: 400V
LL
AC 10(65)A
(dir
ect connection)
V
LN
: 113V to 265V
LN
V
LL
: 196V to 460V
LL
AV9: 400V
LL
AC - 10(65)A
(dir
ect connection)
V
LN
: 113V to 265V
LN
V
LL
: 196V to 460V
LL
Options
PF:
Certified according to MID Directive, Annex "B" + Annex
"D" for legal metrology relevant to active electrical energy
meters (see Annex MI-003 of MID). Can be used for fiscal
(legal) metrology.
System
3: 3-phase, 4-wire
Inputs/Outputs
XX: none
O2: dual open collector
type (dual pulse or one
pulse + one alarm or
dual alarm)
IS: 3 digital inputs for tarif
f
selection or Gas/W
ater/
remote heating meter-
ing plus RS485 port
DP: Dupline port plus 3 dig-
ital inputs for Gas/
water/ remote heating
metering
Power supply
X: Self power supply
(See “Power supply
specifications”)
D: 115/230V
AC (50Hz)
NOTE: please check the
availability of the needed
code on the verification path
diagram below before order.
How to order
provided with digital outputs
that can be either for pulse pro-
portional to the active (imported
and exported) and reactive
energy being measured or for
alarm outputs. In alternative the
RS485 communication port and
3 digital inputs or Dupline port
and 3 digital inputs are avail-
able as an option.
Certified according to MID Directive, Annex
"B" + Annex "D" for legal metrology relevant to
active electrical energy meters (see Annex MI-
003 of MID). Can be used for fiscal (legal)
metrology. Only the total positive energy meter is certified
according to MID.
MID
AV5 3
XX
O2
IS
DP
D
PF
Range
System
Input/Output
Power supply
Option
AV9 3
XX
O2
IS
XPF
Range
System
Input/Output
Power supply
Option
AV2
3
X
Measurement
A: The power is always
integrated (both in case
of positive -imported -
and negative -exported-
power) and the total
ener
gy meter is certi-
fied accor
ding to MID.
B: Only the total positive -
imported- ener
gy meter
is certified accor
ding to
MID. The negative -
exported-ener
gy meter
is not certified accor
ding
to MID.
A
B
Measurement
PF
A
B
Measurement
A
B