Datasheet

Specifications are subject to change without notice (16.10.06) 3
DPB01, PPB01
Adjust the input range set-
ting the DIP switches 3 and
4 as shown below.
Select the desired function
setting the DIP switches 1
a
nd 2 as shown below.
To access the DIP swiches
open the grey plastic cover
as shown below
Selection of level and time
delay:
Upper knob:
Setting of lower level on rel-
ative scale.
Centre knob:
Setting of upper level on rel-
ative scale.
Lower knob:
Setting of delay on alarm
t
ime on absolute scale (0.1
t
o 30 s).
Function/Range/Level and Time Delay Setting
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
M
onitored voltage
ON: Phase-Neutral
OFF: Phase-Phase
Measuring range
SW3 ON ON OFF OFF
SW4
ON OFF ON OFF
M23 Ph-Ph 208 VAC 220 VAC 230 VAC 240 VAC
Voltage
M48 Ph-Ph 380 VAC 400 VAC 415 VAC 480 VAC
Voltage DPB01CM48,
DPB01CM48N
only
M48 Ph-N 220 VAC 230 VAC 240 VAC 277 VAC
Voltage DPB01CM48,
DPB01CM48N
only
Operation Diagrams