Datasheet

Specifications are subject to change without notice (25.11.05) 3
Adjust the input range set-
ting the DIP switches 1 and
2 as shown in figure.
Select the desired function
setting the DIP switches 3 to
6 as shown in figure.
To access the DIP switches
open the plastic cover as
shown in figure.
Selection of level and time
delay:
Upper knob:
Setting of hysteresis on rela-
tive scale: 0 to 30% on set
value.
Centre knob:
Current level setting on rela-
tive scale: 10 to 110% on
full scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
DIB71
Function/Range/Level and Time Delay Setting
Relay working mode
ON: Normally De-energized
OFF: Normally Energized
Measuring range
SW1 ON ON OFF
SW2 OFF ON ON
5MA 1 mA 2 mA 5 mA
50MA 10 mA 20 mA 50 mA
500MA 100 mA 200 mA 500 mA
5A 1 A 2 A 5 A
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over current
OFF: Under current
N (-)
m
Z1
Y1
Y2
A1 A3
A2 15
16 18
L
I
N (-)
PE
m
Z1
Y1
Y2
A1 A3
A2 15
16 18
L
I
Wiring Diagrams
48/230 VAC 24/115 VAC
48/230 VAC 24/115 VAC
Latch/Inhibit
enable
Example 1
Example 2