Datasheet

2 Specifications are subject to change without notice (19-11-02)
Mode of Operation
Function Aa - Asymmetri-
cal Recycler ON-time peri-
od first
The relay operates and the
ON-time period (T1) begins
as soon as the power sup-
ply is connected. After the
ON-time period the relay
releases for the OFF-time
period (T2). This sequence
continues until the power
supply is interrupted for at
least 200 ms.
Function Ab - Asymmetri-
cal Recycler OFF-time
period first
The OFF-time period (T1)
begins as soon as the pow-
er supply is connected.
After the OFF-time period
the relay operates for the
ON-time period (T2). This
sequence continues until
the power supply is inter-
rupted for at least 200 ms.
Wiring Diagram
Operation Diagrams
Function Aa - Asymmetrical Recycler - ON first
Power supply
Relay ON
LED
Function Ab - Asymmetrical Recycler - OFF first
DCB51
Supply Specifications General Specifications
Power Supply Overvoltage cat. II
Rated operational voltage (IEC 60664, IEC 60038)
trough terminals A1, A2: 24 VDC +10% -15% and
24 to 240 VAC +10% -15%
45 to 65 Hz
Voltage interruption 10 ms
Rated operational power 1.5 W
Power ON delay 150 ms
Power OFF delay 200 ms
Indication for
Power supply status LED, green
Output status LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 2 (IEC 60664)
Operating temperature -20 to +60 °C, R:H: < 95%
Storage temperature -30 to +80 °C, R:H: < 95%
Weight Approx 100 g
Screw terminals
Tightening torque Max. 0.5 Nm according to
IEC EN 60947
EMC Electromagnectic Compatibility
Immunity According to EN 61000-6-2
Emission According to EN 50081-1
Approval UL
CE Marking Yes
Function/Range/Time Setting
Setting of function:
No connection between
terminals A1 and Y1:
Aa - asymmetrical recy-
cler (ON first)
Connection between ter-
minals A1 and Y1:
Ab - asymmetrical recy-
cler (OFF first)
Upper knob:
T1 time range setting
Setting of T1 time range.
Centre top knob:
Time T1 setting on relative
scale: 1 to 10 with respect
to the chosen range.
Centre bottom knob:
Setting of T2 time range.
Lower knob:
Time T2 setting on relative
scale: 1 to 10 with respect
to the chosen range.
Power supply
Relay ON
LED
ON/OFF first
ON
OFF
ON
OFF