Datasheet
2 Specifications are subject to change without notice (19-11-02)
Wiring Diagrams
DCB01, PCB01
Supply Specifications General Specifications
Power Supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
trough terminals:
(DCB01C) A1, A2: 24 VDC ± 15 % and
(PCB01C) 2, 10: 24 to 240 VAC +10% -15%
45 to 65 Hz
(DCB01D) A1, A2: 24 to 240 VAC/DC
(PCB01D) 2, 10: +10% -15%, 45 to 65 Hz
Voltage interruption ≤ 10 ms
Rated operational power 1.5 W
Power ON delay ≤ 100 ms
Power OFF delay ≤ 200 ms
Indication for
Power supply status LED, green
Output status LED, yellow (flashing when
timing)
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3 (DCB01), 2 (PCB01)
(IEC 60664)
Operating temperature -20 to +60 °C, R:H: < 95%
Storage temperature -30 to +80 °C, R:H: < 95%
Weight Approx 100 g
Screw terminals (DCB01)
Tightening torque Max. 0.5 Nm according to
IEC EN 60947
EMC Electromagnectic Compatibility
Immunity According to EN 61000-6-2
Emission According to EN 50081-1
Timer Specifications According to EN 61812-1
Approval UL
CE Marking Yes
Function/Range/Time Setting
Upper knob:
Setting of function:
Aa - asymmetrical recy-
cler (ON first)
Ab - asymmetrical recy-
cler (OFF first)
Sh - One shot time func-
tion
Dt - Two-state delay on
operate (2 x SPDT ver-
sions)
Centre knob:
Time T1 setting on relative
scale: 1 to 10 with respect
to the chosen range.
Lower knob:
Time T2 setting on relative
scale: 1 to 10 with respect
to the chosen range.
Selection of time ranges
Adjust the T1 time range
setting the DIP-switches 1
to 3 and the T2 time range
setting the DIP-switches 4
to 6 as shown on the left.
To access the DIP-switches
open the plastic cover using
a screwdriver as shown
below.
T1 time range
ON ON ON: 0.1 to 1 s
ON ON OFF: 1 to 10 s
ON OFF ON: 6 to 60 s
ON OFF OFF: 60 to 600 s
OFF ON ON: 0.1 to 1 h
OFF ON OFF: 1 to 10 h
OFF OFF ON: 10 to 100 h
T2 time range
ON ON ON: 0.1 to 1 s
ON ON OFF: 1 to 10 s
ON OFF ON: 6 to 60 s
ON OFF OFF: 60 to 600 s
OFF ON ON: 0.1 to 1 h
OFF ON OFF: 1 to 10 h
OFF OFF ON: 10 to 100 h