Instruction manual
47
WM5-96 Instruction Manual
AC/DC voltage 90 to 260V (standard)
18 to 60V (on request)
Power consumption ≤ 30VA/12W (90 to 260V)
≤ 20VA/12W (18 to 60V)
Supply Specifications
P
ulse voltage (1.2/50µs)
E
N61000-4-5
Safety standards IEC60664, IEC61010-1
E
N60664, EN61010-1
Measurement standards IEC60688, EN60688,
EN62053-22, EN62053-23,
ANSI C12.20, ANSI C12.1
Approvals CE, cURus and CSA
Connections 5(6) A Screw-type
max. 2.5 mm
2
wir
e
s
(2x 1.5mm
2
);
max screw tightening
torque: 0.5Nm
Housing
Dimensions 96x96x140 mm
Material ABS,
self-extinguishing: UL 94 V-0
Protection degree Front: IP65 / NEMA 4x
Weight Approx. 600 g
(packing included)
O
perating
-
10° to +45°C (14° to 113°F)
temperature (R.H. < 90% non-condensing)
Limit range of operating temp. -20° to +55°C (-4° to 131°F)
(R.H. <90% non-condensing)
Storage -30° to +60°C (-22° to 140°F)
temperature (R.H. < 90% non-condensing)
Installation category III
Pollution degree 2
Altitude up to 2000m (6560 feet) above
s
ea-level
I
nsulation reference voltage
3
00 V
R
MS
t
o ground (AV5 input)
Dielectric str
ength
4k
VAC
RMS
(for 1 min)
Noise Rejection
CMRR 100 dB, 48 to 62 Hz
EMC
Emissions EN61000-6-3, EN60688
residential environment,
commerce and light industry
ANSI/IEEE C37.90-1989
(surge, withstand and fast
transient test)
General Specifications
Revenue Approval Settings
Technical Specifications
• The access to the programming parameters via front key pad and/or serial communication ports is locked.
• The front key pad (up and down keys) allows the displaying of the variables only, while the communication ports allows the
transmission of the variables only
.
• A proper “instrument settings” form must be filled up by the user before equipment supplying.
• WM5-96 is supplied with the desired modules plugged and sealed in the proper slots.
• WM5-96 fulfils: the ANSI/IEEE C12.20-1998 requirements;
the CAN3-C17-M84 requir
ements;
and can be certified according to:
C12.20-1998, class 0.5 (independent labs);
AE-0924 Industry Canada Approval.