Indication
Normal mode
Green LED Yellow LED Power Output
OFF OFF OFF OFF
ON OFF ON OFF
ON ON ON ON
Output short circuit
Green LED Yellow LED Output
OFF Flashes 4Hz Yellow LED ashes minimum 1 sec.
Teach by wire
Out of the box (Factory settings):
Typically, the sensor can be used without any additional calibration; it is designed to work with plastic tank
walls of approximately 0,5 to 6 mm in thickness and glass walls of approximately 0,5 to 4 mm in thickness. It
is important that the glass or plastic is nonconductive.
Calibration:
If the factory settings are insu󰀩cient, the sensor is teachable to either Full or Empty.
Calibration Full:
The sensor switch point is set below the actual detection value to ensure that slight changes in the application
will not a󰀨ect the sensing performance.
In most applications, the full calibration on a full tank or tube will be su󰀩cient.
In critical applications with large variations in media type and temperature, it can be an advantage to teach the
Full level with approximately 50 % of the active sensing surface covered.
Full calibration procedure:
•Connect teach wire to V+ for 2 - 7 seconds
•The green LED ashes 1 imp. per sec. and the yellow LED is OFF
•After successful calibration, the yellow LED ashes 3 times (with 1 Hz)
Calibration Empty:
The sensor switch point is set above the actual detection value to ensure that slight changes in the application
will not a󰀨ect the sensing performance.
In most applications, the Empty calibration on an empty tank or tube will be su󰀩cient.
In critical applications with a high amount of residue lm, moisture or foam build-up, an Empty calibration can
be performed with the build-up present.
Empty calibration procedure:
•Connect teach wire to V+ for 7 - 12 seconds
•The green LED ashes 1 imp. per sec. and the yellow LED is ON
•After successful calibration, the yellow LED ashes 3 times (with 1 Hz)
Cancel calibration procedure:
•Keep the teach wire connected to V+ for more than 14 seconds to abort teach procedure. The switch points
will remain unchanged.
•The green LED is o󰀨 and the yellow LED ashes (4 Hz)