User guide

Carlin part number MNEZ123 Rev. 07/13/11
– 5 –
Model EZ-1/2/3 oil burners — Instruction manual
2. Prepare site • assemble burner • mount burner
Inspect/repair/replace vent system
Donotinstallthisburnerunlessyouhaveveriedtheentire
vent system and the appliance are in good condition and
complywithallapplicablecodes.And...
The vent and chimney must be sized and constructed in
accordance with all applicable codes.
Donotinstalloruseanexistingmanualdamperinthebreech-
ing(ventconnector)orchimney.
Donotconnecttheapplianceventconnectortoachimney
or vent serving a fireplace, incinerator or solid-fuel-burning
apparatus.
In a cold climate, do not vent into a masonry chimney that
has one or more sides exposed to the outside. Install a listed
stainlesssteellinertoventtheueproducts.
Adefectiveventsystemcouldresultinseverepersonalinjury,
death or substantial property damage.
Prepare vent/chimney
• Secureallmetalventjointswithscrews,followingtheventmanufac-
turer’s instructions.Seal all joints in thevent system and chimney.
Repairmasonrychimneyliningandrepairallmortarjointsasneeded.
• Install a barometric draft regulator in the vent piping if specified in the
appliance manual. (The damper must be located in the same space
astheappliance.)
• Providesupportfortheventpiping.Donotresttheweightofanyofthe
ventpipingontheapplianceueoutlet.
Combustion/ventilation air openings
Even if combustion air is piped to an (optional) burner
air intake adapter, the boiler room must still have the
minimum air openings listed in Table 2 and described in the
following paragraphs. This is to provide needed ventilation to
keep the burner and appliance cool and to avoid the boiler
room developing negative pressure.
ThecombustionairopeningsMUSTbesizedbasedonthe
total input of all appliances in the room.
Check appliance manual and applicable codes for required sizing/design/
placement of combustion/ventilation air openings. You can use the follow-
inggeneralguidelines,takenfromNFPA31,providedtheymeetalllocal
requirements.
Louvers/screens
• Airopeningsizesarealwaysgiveninfreearea.Thismeansafterde-
duction for louver obstruction. If you can’t find the louver reduction for
the grilles used, assume free area is 20% of total for wood louvers, or
60% of total for metal louvers.
• Screenscanbenonerthan¼-inchmesh,andmustbeaccessible
for cleaning.
Residential installations
Unconnedspaces(atleast7,000cubicfeetperGPH)
• Anunconnedspacemeansaroomwithatleast7,000cubicfeetvol-
umeforeachGPHinput(or50cubicfeetperMBH)ofall appliances
in the room.Example:Foreach1GPHoilinput,theroommusthave
7,000cubicfeet(875squarefeetwithan8-footceilingheight.)
Table 2 Minimum combustion/ventilation air openings
• Openbasementsandcrawlspacesareusuallylargeenough,andwill
generally allow enough air infiltration so special provisions will seldom
be required.
• If the building is tightly constructed, you will have to provide outside
air openings into the building. The total free area of the openings must
beatleast1squareinchper5,000Btuh(28squareinchesperGPH)
of all appliances in the space.
• SeeTable2forsummary.
Air openings to confined spaces
(less than 7,000 cubic feet per GPH)
• Airtakenfrominsidebuildingonly—
• Providetwoopenings—onenearoor,theothernearceiling.Provide
freeareaof140 square inches per GPH input. If buildingistightly
constructed,provideairopening(s)intobuildingproviding30square
inchesperGPHaswell.
• Airtakenfromoutside—
• Directthroughoutsidewallorverticalducts:Providetwoopenings—one
nearoor,theothernearceiling.Providefreeareaof35squareinches
perGPHinput.
• Throughhorizontalducts:Providetwoopenings—onenearoor,theother
nearceiling.Providefreeareaof70squareinchesperGPHinput.
• Ventilation air from inside/combustion air from outside
Sizeopeningstointeriortoprovide140squareinchesfreeareaperGPHinput.
Sizeoutsideairducttoprovide28squareinchesfreeareaperGPH.
• SeeTable2forsummary.
Source
of air
Mininimum
free area
of opening(s)
Total grill area, typical (sq. in.)
for firing rates of:
1 GPH 2 GPH 3 GPH
Wood Metal Wood Metal Wood Metal
Residential installations,
unconfined spaces (7,000 cu. ft. volume per GPH)
From inside building,
typical construction
No special openings required if natural inltriation is sufcient.
From inside building,
tight construction
1 or more grilles
30 Sq. in./ GPH
150
50 300 100 450 150
Residential installations, confined spaces
From inside building
through interior walls
2 openings, each
140 Sq. in./ GPH
700 234 1400 467 2100 700
From outside building
direct through outside
wall
2 openings, each
35 Sq. In./ GPH
175 59 350 117 525 175
From outside building
through vertical ducts
2 openings, each
35 Sq. In./ GPH
175 59 350 117 525 175
From outside building
through horizontal
ducts
2 openings, each
70 Sq. In./ GPH
350 117 700 234 1050 350
Ventilation through
interior walls, with an
opening to outside
2 Int. openings,
each
140 Sq. In./ GPH
1 Exterior opening
28 Sq. In./ GPH
700
140
234
47
1400
280
467
94
2100
420
700
140
Commercial installations
From outside building
direct through adjacent
outside wall
One opening through outside wall, providing free area of at least
28 Square inches per GPH input
Other conditions
Size openings per local codes/jurisdictions