Carlin U – Residential Oil Burners – Page 78
What does cadmium sulfi de do?
Cadmium sulfi de is an electrical conduc-
tor.
When cadmium sulfi de is exposed to
visible light, its resistance changes. The
stronger the light source, the lower the
resistance.
When the burner isn’t fi ring, with the
cad cell inside and not exposed to any
light, the cad cell has a high resistance
(over 50,000 ohms).
When the burner fl ame starts, the cad
cell sees the light from the fl ame, and its
resistance drops.
The primary control (48245, 60200, for
examples) knows fl ame is present be-
cause it senses this resistance change.
Fixed resistance primary test
Use this method to test the performance of
a primary control, removing the cad
cell as a factor.
• Remove the cad cell wires
from the primary control’s
“F-F” terminals.
• Connect one end of a
¼-watt, 1500 ohm (1.5 k)
resistor to one of the “F-F”
terminals.
• Start the burner. AFTER
ame has been established,
connect the other end of the 1.5
k resistor to the other “F-F” terminal.
If the primary control is operating cor-
rectly, it should accept this resistance
and operate normally. If the control does
not operate correctly, replace the con-
trol.
Remove the resistor and replace the cad
cel leads on the “F-F” terminals.
Cad
Cells
Cad cell construction
A cad cell contains:
a sensing plate coated with cadmium
sulfi de.
a metal grid on the cadmium sulfi de
to supply the two connections from
the sensor.
a clear coating over the cadmium
sulfi de and grid that prevents con-
tamination from moisture, dirt and
oil.
a housing to mount the sensor as-
sembly.
Carlin U – Residential Oil Burners – Page 78
Carlin U – Residential Oil Burners – Page 78
• Remove the cad cell wires
from the primary control’s
“F-F” terminals.
• Connect one end of a
¼-watt, 1500 ohm (1.5 k
resistor to one of the “F-F”
terminals.
• Start the burner. AFTER
ame has been established,
connect the other end of the 1.5
k
resistor to the other “F-F” terminal.
If the primary control is operating cor-
If the primary control is operating cor-
rectly, it should accept this resistance
and operate normally. If the control does
not operate correctly, replace the con-
trol.
Remove the resistor and replace the cad
Remove the resistor and replace the cad
cel leads on the “F-F” terminals.