Instruction Manual

Model 702GAS Advanced gas burners — Instruction manual
Carlin part number MN702G Rev. 03/14/11
– 16 –
Where appliance instructions differ from this manual, follow the appliance instructions.
5. Checkout procedure — before starting the burner
Before firing the burner . . .
Should overheating or an emergency occur, im-
mediately do the following:
• Shutoffgassupplyvalve.
Undersomecircumstancespowershouldremain
on for water pumps or blowers. Determine proper
response before attempting start-up.
• Ifburnerfailsignitiononseveralattempts,use
burner blower to purge appliance chamber
before restart.
Checklist before firing . . .
Burner and appliance installed per this manual and appliance
instruction manual?
Burner/appliance installed per all applicable codes?
Installation site has adequate combustion/ventilation air open-
ings and vent system?
Are voltages correct? Burner, appliance and motor correctly
wired per burner and appliance manuals and wiring diagrams?
Gas manifold spud orifices (on gas manifold, item 29, page 5)
sealed with pipe dope and tight?
Gas supply line in good condition, sized and designed correctly?
Gas line connections and fittings tight?
Burner, appliance and all components inspected and in good
condition?
Appliance limit and operating controls properly installed, wired
and adjusted?
Boiler water supply, feed pumps, automatic feeders, and low
water cut-offs properly piped and wired?
Breeching, draft regulator, draft inducer (if required) properly
installed and operational?
Gas train piping and components correctly installed, tested and
verified gas tight?
Vent lines installed when required?
Gas lines purged?
Sufficient gas line pressure present?