Install Instructions

Startup & Operation (continued)
TFI The CAD cell must sense ame within the TFI time limit (trial for ignition). Insufcient ame puts control into
lockout.
Run The burner continues firing during call for heat if the CAD cell is sensing flame. Only the green LED is on
during normal running.
Lockout If CAD cell does not sense ame within the TFI time limit after the burner starts, lockout occurs. The con-
trol turns the red LED on constant and closes the alarm contact.
To Reset Push in and hold reset button for 2 seconds, then release.
Latch-up If the control locks out 3 times during a single call for heat, latch-up occurs. The control turns on both the
amber and red LEDs constant. You must use the special procedure below to reset the control after latch-
up.
Reset after latch-up: only a qualified service technician should attempt to reset the control after latch-up.
The problem that caused the repeated burner lockouts must be corrected before returning the burner to
normal operation.
Push in and hold the reset button for 10 seconds. The amber LED will begin to ash.
After the LED begins flashing, continue holding the reset button for 20 seconds. The LEDs will turn off.
Release the reset button and the control will restart (releasing the button before the LEDs turn off will
cause the control to remain in latch-up).
The 60200 control will not reset from lockout or latch-up if power is interrupted.
Flame If the CAD cell loses ame signal during operation (after the TFI), the red LED ashes. The burner shuts off
failure within 2 seconds. Recycle: Control waits for 65 seconds (with red LED flashing), then begins again at Self-
test 2. Red LED goes off.
If the green LED is blinking during a run, the ame is weak or unstable which may cause recycle.
Motor delay Set thermostat (or Aquastat) to stop call for heat. The oil valve (if installed) will turn off within 2 seconds.
OFF The motor remains on for the motor delay off period (post-purge), then turns off. (If no oil valve is wired to
the control, the burner shuts off within 2 seconds after end of call for heat. There is no post-purge.)
Stand-by Control remains in stand-by mode until limit circuit sends power to the black wire and thermostat circuit
closes (call for heat).