Replacement Parts List
22
Parts List m Items that are shaded are considered stock items and will ship in 3-5 days.
COMMERCIAL
OIL
CONTROL PANELS & OPTIONS
Optional Control Sets
Optional Control Package Substituted is:
Control Set
Part Number
Relay
Part Number
Notes
FIREYE ULTRA-VIOLET SCANNERS
EMX24UV MP230
Fireye Control (1, 5, 6)--Non-Recycling, 4 Sec. TFI, 4 Sec. Flame Stabilization Period, 4 Sec. FFRT, 30 Sec. Pre-
Purge, MP230 Programmer, 61-3060 Sub-Base, MAUV1 Amplifier, UV1A Scanner.
HONEYWELL ULTRA-VIOLET SCANNERS
EMX15UV RM7897C
1000 Honeywell Control (1, 5, 6)--Field Selectable Recycling, 10 Sec. TFI, 3 Sec. FFRT, 30 Sec. Pre-Purge, 15 Sec
Post-Purge, R7849A 1023 UV Amplifier, Q7800B 1003 Sub-Base, C7027A 1023 Scanner, ST7800A 1039 Timing
Card.
EMX39UV RM7897A
1002 Honeywell Control (1, 5, 6)--Field Selectable Recycling/Non-Recycling, 10 Sec. TFI. Field Selectable
0.8/3.0 Sec. FFRT, 30 Sec. Pre-Purge, Q7800B 1003 Sub-Base, C7027A 1023 UV Scanner, R7849A 1023 UV
Amplifier, ST7800A 1039 Timing Card.
EMX43UV RM7840L
1075 Honeywell Control (3, 4, 6)--Field Selectable Recycling, 10 Sec. TFI, Field Selectable 3.0 FFRT, 30 Sec.
Pre-Purge, 15 Sec. Post-Purge, Q7800B 1003 Sub-Base, C7027A 1023 UV Scanner, R7849A 1023 UV Amplifier,
ST7800A 1039 Timing Card. Over 20 GPH Control Package.
EMX43UVSC RM7840L
1075 Honeywell Control (2, 3, 4, 6)--Field Selectable Recycling, 10 Sec. TFI, Field Selectable 3.0 FFRT, 30 Sec.
Pre-Purge, Q7800B 1003 Sub-Base, C7027A 1023 UV Scanner, R7849B 1021 UV Amplifier SC, ST7800A 1039
Timing Card. Over 20 GPH Control Package.
HONEYWELL INFRA-RED SCANNERS
EMX45UVSC RM7840L
1075 Honeywell Control (2, 3, 4, 6)--Field Selectable Recycling, 10 Sec. TFI, Field Selectable 3.0 FFRT, 30 Sec.
Pre-Purge, 15 Sec. Post-Purge, Q7800B 1003 Sub-Base, C7915A1010 IR Scanner, R7852B1009 Amplifier (Self
Check), ST7800A 1039 Timing Card. Over 20 GPH.
VISUAL DISPLAY
Fireye 97271 ED 510 Display Module
Honeywell 97719 RM 7800 Display Module
CAD CELL CONTROL SETS (SEE NOTE 1)
40E 40200-02
Carlin Interrupted Duty Control – Recycling - 15 Sec.TFI, 10 Sec. Flame Stabilization Period. CAD Cell Flame
Detector.
50E 50200-02
Carlin Interrupted Duty Microprocessor – Recycling - 15 Sec. TFI, CAD Cell Flame Detector, Alarm Contacts.
70E 70200
Carlin Fully Adjustable Control – with Alarm and Blocked Vent Contacts.
NOTES
1. All control packages meet CSD-1, Mass Code, UL-296, and NYC-BAR codes for under 20 GPH.
2. Meets Mass Code over 20 GPH where noted.
3. Meets UL-296 over 20 GPH where noted.
4. Meets NYC-BAR Code over 20 GPH and under 30 GPH where noted.
5. Can be installed on all units under 20 GPH.
6. Selected units meet IRI requirements with additional sensors installed. In addition to a non-recycling control, IRI requires the installation of a low oil pres-
sure switch and an airflow switch.
7. Air flow switch, low oil pressure switch, and safety oil valve required for IRI. Air flow switch and safety oil valve required for FM. 70200 control does not
meet IRI or FM requirements.
To substitute an optional control package for the standard control included in the chassis only price
(Models 201CRD thru 801CRD) or the burner price (Models 1050FFD and 1150FFD), do the following:
1. Select optional control package to be substituted.
2. Add control package cost, as shown in “Price Adder” column to base burner cost.
Note: Air ow switch, low oil pressure switch, and safety oil valve required for IRI. Air ow switch and safety oil valve
required for FM. 6020002 control does not meet IRI or FM requirements.