Product Overview

E Series Oil Primary Controls
Models 40200, 42230, 50200, 60200
The E Series mixes new technological features and upgrades
with the same Carlin quality that’s come standard on all our
products. A “Like-for-Like” replacement for their respective
controls, the E Series offers a newly updated, competitively
priced and easy to use product.
Features
Updated features based off the
40200, 42230, 50200, 60200
control models
• Interrupted duty ignition
• LED indicators
• Recycle on flame failure
• Serviceman reset protection
• Pump prime
• SMC technology
Alarm contacts
(models 50200, 60200)
Flame signal test jack
(models 50200, 60200)
Valve delay On / Motor delay Off
(models 50200, 60200)
Specifications
40200, 42230
Power Input (from limit circuit) ............. 120VAC, 60Hz, 10VA
Motor Load .................................................... 10FLA, 60 LRA
Ignitor Load ..................................... 120 VAC, 60Hz, 500 VA
Operating Temperature Limits .....................+32°F to +140°F
Storage Temperature Limits ........................ -40°F to +185°F
Thermostat Anticipator Current ............................... 0.2A, AC
CAD Cell Resistance (with flame) ....................R<1500 ohms
Agencies ............................... UL Recognized (US & Canada)
50200
Power Input (from limit circuit) ............... 120VAC, 60Hz, 9VA
Motor Load .................................................... 10FLA, 60 LRA
Ignitor Load ..................................... 120 VAC, 60Hz, 500 VA
Alarm Contacts .............................................24V, AC/DC, 2A
Operating Temperature Limits .................... +32°F to +140°F
Storage Temperature Limits ........................ -40°F to +185°F
Thermostat Anticipator Current ............................... 0.2A, AC
CAD Cell Resistance (with flame) ....................R<1500 ohms
Agencies ............................... UL Recognized (US & Canada)
60200
Power Input (from limit circuit) ............... 120VAC, 60Hz, 9VA
Limit Circuit Input (black wire) .......................120VAC, 60 Hz
Motor Load .................................................... 10FLA, 60 LRA
Ignitor Load ..................................... 120 VAC, 60Hz, 500 VA
Alarm Contacts .............................................24V, AC/DC, 2A
Operating Temperature Limits .................... +32°F to +140°F
Storage Temperature Limits ........................ -40°F to +185°F
Thermostat Anticipator Current ............................... 0.1A, AC
CAD Cell Resistance (with flame) ....................R<1500 ohms
Agencies ............................... UL Recognized (US & Canada)