User manual
47
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
13.4 Models of concentrated jet steam distributors
UEX models
code
UE001X
UE003X
UE005X
UE008X
UE009X
UE010X
UE015X
UE018X
UE025X
UE035X
UE045X
UE065X
UE090X
UE130X
steam outlet dia.
mm (in)
22
(0.9”)
22
(0.9”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
40
(1.6”)
40
(1.6”)
40
(1.6”)
2x40
(2x1.6”)
2x40
(2x1.6”)
4x40
(2x1.6”)
max. capacity
kg/h (lb/h)
1/1.5
(2.2/3.3)
3
(6.6)
5
(11)
8
(17.6)
9
(19.8)
10
(22)
15
(33)
18
(39.7)
25
(55.1)
35
(77.2)
45
(99.2)
65
(143.3)
90
(198.4)
130
(286.6)
CAREL distributors jet concentrated
code steam inlet dia.
mm (in)
max. capacity
kg/h (lb/h)
SDPOEM0012 22 (0.9”) 3 (6.6) 1 1 --------- - - -
SDPOEM0022 30 (1.2”) 18 (39.7) 1 1 111111- - - - - -
SDPOEM0000 30 (1.6”) 18 (39.7)
(with 30mm/1.6” hole)
1 1111111(2)* (2)* (4)** (4)**
Tab. 13.d
1 = the humidi er is connected to just one distributor
(2) = the humidi er is connected to two distributors (using the “Y” kit: UEKY000000)
2 = the humidi er is tted with two outlets and can be connected to two distributors
(4) = the humidi er is tted with two outlets and can be connected to up to four distributors (using two “Y” kits)
* = use CAREL “Y” kit code UEKY000000 (40 mm/1.6” inlet and 2 x 30 mm/1.2” outlets)
** = use CAREL “Y” kit code UEKY000000 (40 mm/1.6” inlet and 2 x 30 mm/1.2” outlets)
13.5 Models of linear distributors
UEX models
code
UE001X
UE003X
UE005X
UE008X
UE009X
UE010X
UE015X
UE018X
UE025X
UE035X
UE045X
UE065X
UE090X
UE130X
steam outlet dia.
mm (in)
22
(0.9”)
22
(0.9”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
40
(1.6”)
40
(1.6”)
40
(1.6”)
2x40
(2x1.6”)
2x40
(2x1.6”)
4x40
(2x1.6”)
max. capacity
kg/h (lb/h)
1/1.5
(2.2/3.3)
3
(6.6)
5
(11)
8
(17.6)
9
(19.8)
10
(22)
15
(33)
18
(39.7)
25
(55.1)
35
(77.2)
45
(99.2)
65
(143.3)
90
(198.4)
130
(286.6)
CAREL DP linear distributors
code steam inlet
dia.
mm (in)
max. capacity
kg/h (lb/h)
length
mm (in)
DP035D22R0 22 (0.9”) 4 (8.8) 332 (13.1) 1 1 --------- - - -
DP045D22R0 22 (0.9”) 6 (13.2) 438 (17.2) 1 1 --------- - - -
DP060D22R0 22 (0.9”) 9 (19.8) 597 (23.5) 1 1 --------- - - -
DP085D22R0 22 (0.9”) 9 (19.8) 835 (32.9) 1 1 --------- - - -
DP035D30R0 30 (1.2”) 5 (11) 343 (13.5) - - 1 -------- - - -
DP045D30R0 30 (1.2”) 8 (17.6) 427 (16.8) - - 1 1 ------- - - -
DP060D30R0 30 (1.2”) 12 (26.5) 596 (23.5) - - 1111- - - - - - - -
DP085D30R0 30 (1.2”) 18 (39.7) 850 (33.5) - - 111111(2)* - - - - -
DP105D30R0 30 (1.2”) 18 (39.7) 1048 (41.3) - - 111111(2)* - - - - -
DP125D30R0 30 (1.2”) 18 (39.7) 1245 (49) - - 111111(2)* - - - - -
DP085D40R0 40 (1.6”) 25 (55.1) 834 (32.8) - - ------1(2)** (2)** (4)** - -
DP105D40R0 40 (1.6”) 35 (77.2) 1015 (40) - - ------11(2)** 2 (4)** 4
DP125D40R0 40 (1.6”) 45 (99.2) 1022 (40.2) - - ------111 2 2 4
DP165D40R0 40 (1.6”) 45 (99.2) 1636 (64.4) - - -------11 2 2 4
DP205D40R0 40 (1.6”) 45 (99.2) 2025 (79.7) - -
-------12 2 2 -
Tab. 13.e
1 = the humidi er is connected to just one distributor
(2) = the humidi er is connected to two distributors (using the “Y” kit: UEKY000000)
2 = the humidi er is tted with two outlets and can be connected to two linear distributors
(4) = the humidi er is tted with two outlets and can be connected to up to four linear distributors (using two “Y” kits)
* = use CAREL “Y” kit code UEKY000000 (40 mm/1.6” inlet and 2 x 30 mm/1.2” outlets)
** = use CAREL “Y” kit code UEKY40400 (40 mm/1.6” inlet and 2 x 30 mm/1.2” outlets)
For typical installations of the linear distributors, see Fig. 13.f on page 48