13. GENERAL FEATURES AND MODELS
13.1 humiSteam models and electrical speci cations
The following table lists the electrical data relating to the power supply
of the various models and the speci cations of each. Note that some
models may be powered at di erent voltages, obviously with di erent
power input and steam production.
power supply rated speci cations
model steam
production
(2; 4)
(kg/h)
power
(2)
(kW)
code voltage
(1)
(V - type)
current
(2)
(A)
TAM con guration
(5)
cable
(3)
(mm
2
)
line fuses
(3)
(A /
type)
wiring diagram
(Fig.)
UE001 1.5 1.1 D 230 - 1~ 4.9 13.a 100 1.5 10 A / fast-blow 12.1
UE003 3 2.2 D 230 - 1~ 9.8 13.d 300 2.5 16 A / fast-blow 12.1
K 230 - 3~ 5.6 13.a 100 2.5 16 A / fast-blow 12.2
L 400 - 3~ 3.2 13.d 100 1.5 10 A / fast-blow 12.3
UE005 5 3.7 D 230 – 1~ 16.3 13.e 300 6.0 32 A / fast-blow 12.1
K 230 - 3~ 9.4 13.c 300 2.5 16 A / fast-blow 12.2
L 400 - 3~ 5.4 13.a 100 1.5 10 A / fast-blow 12.3
UE008 8 6.0 K 230 – 3~ 15.1 13.c 300 6.0 32 A / fast-blow 12.2
L 400 – 3~ 8.7 13.a 100 2.5 16 A / fast-blow 12.3
UE009 9 6.7 D 230 - 1~ 29.3 13.a 500 10.0 40 A / fast-blow 12.1
UE010 10 7.5 K 230 – 3~ 18.8 13.c 300 6.0 32 A / fast-blow 12.2
L 400 – 3~ 10.8 13.d 300 2.5 16 A / fast-blow 12.3
UE015 15 11.2 K 230 – 3~ 28.2 13.c 500 10.0 40 A / fast-blow 12.2
L 400 – 3~ 16.2 13.a 300 6.0 32 A / fast-blow 12.3
E018 18 13.5 L 400 – 3~ 19.5 13.a 300 6.0 32 A / fast-blow 12.3
UE025 25 18.7 K 230 – 3~ 47.1 13.b 500 25 63 A / fast-blow 12.4
L 400 – 3~ 27.1 13.c 500 16 50 A / fast-blow 12.5
UE035 35 26.2 K 230 – 3~ 65.9 13.b 700 35 100 A / fast-blow 12.4
L 400 – 3~ 37.9 13.b 500 16 60 A / fast-blow 12.5
UE045 45 33.7 K 230 – 3~ 84.7 13.b 700 50 125 A / fast-blow 12.4
L 400 – 3~ 48.7 13.c 700 25 80 A / fast-blow 12.5
UE065 65 48.7 L 400 – 3~ 70.4 13.c 700 35 100 A / fast-blow 12.5
UE090 90 67.5 L 400 – 3~ 97.43 13.b 700 70 125A / fast-blow 12.6
UE130 130 97.5 L 400 – 3~ 140.73 13.b 700 95 160A / fast-blow 12.6
Tab. 13.a
(1)
tolerance allowed on the rated mains voltage: -15%, +10%;
(2)
tolerance on the rated values: +5%, -10% (EN 60335-1);
(3)
recommended values refer to laying PVC or rubber cables in closed conduits, 20 m
(65.6 feet) long; the standards in force must however be observed,
(4)
rated max instant steam production: the average steam production may be a ected
by external factors, such as: ambient temperature, water quality, steam distribution
system;
(5)
refer to the wiring diagrams to verify
the data are not absolute and if these di er from local standards, the latter
must prevail.
TAM con gurations and connections (transformer for
measuring the current)
Important: the con gurations and connections are already made
by CAREL, and no changes are required. The following diagrams
represent possible connection modes and may be useful in the event of
serious electrical malfunctions on the humidi er.
All operations must only be performed by quali ed personnel, improper
use may cause serious damage.
one cable turn one turn of the two cables
of the same phase
two cable turns of the same
phase
one cable in “double turn”
mode
three cable turns of the
same phase
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
Fig. 13.a Fig. 13.b Fig.13.c Fig.13.d Fig.13.e
Important:
to avoid interference, separate the power cables from the probe
•
cables.