User manual
23
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
Remote Off:• isteam production interrupted through the opening of
the “Remote ON/OFF” contact;
OFF by Keyb.:• steam production disabled by keyboard (see “SET”
mask);
Manual Proc.:• humidifer fuctions managed manually (maintenance
menu > manual procedure);
No request:• humidifer on, without steam production request.
Hour counter display UOM
Total hours
value h
Cylinder 1
Operating hours
value h
Cylinder 2
Operating hours
value h
Time bands active
YES/NO
Current
Info cylinder 1 display UOM
Cyl. prod.
value kg/h
Status
(*)
Activity
cylinder activty (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
Info cylinder 2 display UOM
Cyl. prod.
value kg/h
Status
(*)
Activity
activity of the cylinder (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
(*) cylinder status:
Off• : stop steam production (no request or signalling of an alarm)
Softstart• : starting steam production;
Operating• : steady operation steam production;
Low Prod• .: low production;
Washing• : cylinder washing in progress.
(**) Activity of the cylinder:
Cyl.Off• : stop steam production (no request or signalling of an
alarm);
Fill• : ll valve operating;
Evaporation• : steam production operating;
Drain• : drain pump operating;
Stop by Al.• : steam production stopped by an alarm;
Inact.Drain• : total drain for inactivity;
Pre-clean• : new cylinder washing in progress;
M. Emptying• : manual drain;
Chk.F.Water• : ll water check (from lack of water cylinder alarm);
Period FI:• Periodical drain for dilution.
6.7 “SET” screen
Used to set the main values for the humidi er.
To access, press ENTER from the “Main” screen, to move from one value to
the next press UP (next) or DOWN (previous) and ENTER to con rm.
Press ESC repeatedly to return to the “Main” screen.
Parameter range default UOM
Set point 0 to 100
50 %rH
Humidifier AUTO / OFF
AUTO
Max. prod. 20 to 100
100 %
Prop. band. 2 to 19.9
5 %rH
Lim. probe set * 0 to 100
80 %rH
Prop. band * 2 to 19.9
5 %rH
* visible only if the limit probe is enabled
Manual drain:
• access the “SET” screen,
• press UP and DOWN together for 5 seconds
The same procedure can be repeated to stop the drain cycle