Remote Off: isteam production interrupted through the opening of
the “Remote ON/OFF” contact;
OFF by Keyb.: steam production disabled by keyboard (see “SET
mask);
Manual Proc.: humidifer fuctions managed manually (maintenance
menu > manual procedure);
No request: humidifer on, without steam production request.
Hour counter display UOM
Total hours
value h
Cylinder 1
Operating hours
value h
Cylinder 2
Operating hours
value h
Time bands active
YES/NO
Current
Info cylinder 1 display UOM
Cyl. prod.
value kg/h
Status
(*)
Activity
cylinder activty (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
Info cylinder 2 display UOM
Cyl. prod.
value kg/h
Status
(*)
Activity
activity of the cylinder (**)
Current
value A
Power contactor
YES/NO
Fill valve
YES/NO
Drain pump
YES/NO
(*) cylinder status:
Off : stop steam production (no request or signalling of an alarm)
Softstart : starting steam production;
Operating : steady operation steam production;
Low Prod .: low production;
Washing : cylinder washing in progress.
(**) Activity of the cylinder:
Cyl.Off : stop steam production (no request or signalling of an
alarm);
Fill :  ll valve operating;
Evaporation : steam production operating;
Drain : drain pump operating;
Stop by Al. : steam production stopped by an alarm;
Inact.Drain : total drain for inactivity;
Pre-clean : new cylinder washing in progress;
M. Emptying : manual drain;
Chk.F.Water :  ll water check (from lack of water cylinder alarm);
Period FI: Periodical drain for dilution.
6.7 “SET screen
Used to set the main values for the humidi er.
To access, press ENTER from the “Main screen, to move from one value to
the next press UP (next) or DOWN (previous) and ENTER to con rm.
Press ESC repeatedly to return to the “Main” screen.
Parameter range default UOM
Set point 0 to 100
50 %rH
Humidifier AUTO / OFF
AUTO
Max. prod. 20 to 100
100 %
Prop. band. 2 to 19.9
5 %rH
Lim. probe set * 0 to 100
80 %rH
Prop. band * 2 to 19.9
5 %rH
* visible only if the limit probe is enabled
Manual drain:
access the “SET screen,
press UP and DOWN together for 5 seconds
The same procedure can be repeated to stop the drain cycle