User manual

19
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
5. REMOTE TERMINAL, GSM MODEM AND SUPERVISORY NETWORK
5.1 Remote display terminal
The display terminal can be detached from the humidi er and moved to
another place.
Depending on the distance required, the following are necessary:
up to 50 metres: 6-wire telephone cable and two EMC  lters (code
0907858AXX) (see Fig. 5.a);
up to 200 metres: two CAREL TCONN6J000 boards, 6-wire telephone
cables and an AWG20-22 shielded cable with 3 twisted pairs (for the
connection of the two boards, Fig. 5.b).
Note: to  ll the empty space left by the display terminal on the
humidi er, use CAREL kit code HCTREW0000.
Remote connection of the terminal up to max 50 m
J18
humiSteam
3
2
1
2
Fig. 5.a
Key:
1 telephone cable (up to 50 m distance);
2
EMC  lters (code 0907858AXX) to be applied to the ends of the
telephone cable;
3 remote display terminal.
Remote connection of the terminal up to 200 m
J18
humiSteam
4
2
2
A
J14
1 2 3 1 2 3
J15
B
C
SC
A
J14
1 2 3 1 2 3
J15
B
C
SC
5
3
3
1
Fig. 5.b
Key:
1 telephone cable (up to 0.8 m distance);
2 CAREL TCONN6J000 board;
3 pin strip J14 and J15 in position 1-2 (power supply available on the
telephone connectors A, B and C and screw SC);
4
WG20-22 shielded cable with 3 twisted pairs to move the display
terminal up to 200 m away. Connection to the TCONN6J00 board:
terminal SC function
0 EARTH (shield)
1 +VRL
2 GND
3 RX/TX-
4 RX/TX+
5 GND
6 +VRL
5 remote display terminal
5.2 GSM network connection (send SMS)
The humidi er can be con gured to send SMS message for alarms and
malfunctions (see menu installer > supervisor > GSM protocol).
humiSteam
J19
1
2c
3
MODEM
2a
2d
2b
Fig. 5.c (inside humidi er, electrical compartment)
Key:
1 electronic board PCOI00MDM0 (to be connected to connector J19 on
the humidi er board)
2
CAREL GSM kit PLW0P65M00, made up of:
2.a modem
2.b antenna (with magnetic base)
2.c serial cable
2.d power supply
3 SIM card to be inserted in the modem. Make sure that the access
password (PIN number) is not enabled
5.3 Supervisory network (J19)
The humidi er is equipped serial interface of the following:
PCOS004850 (for connections protocol Carel, Modbus®, Winload)
Instead of the supplied, they can be connected to the following optional
boards:
PCO10000F0 for Lon connections;
PCO100MDM0 for RS232 connections;
+ -
GND
connection terminal block
for RS-485 board
Fig. 5.d (detail of the electronic board, humidi er electrical
compartment)